Main
product specific application
Output filter
Maximum permissible voltage
690 V AC
Complementary
product compatibility
ATV61HC11Y
ATV61HC13Y
ATV61HC16Y
ATV61HC20Y
ATV71HC11Y
ATV71HC13Y
ATV71HC16Y
[in] rated current
240 A
range compatibility
Altivar 61
Altivar 71
Product or component type
Sinus filter
thermal losses
1500 W at 100 Hz
Max current
1.5 x nominal current (duration = 60 s)
switching frequency
4...8 kHz
Net weight
210 kg
Maximum voltage drop at rated load
10 %
Pollution degree
2 conforming to EN 50178
electrical connection
Bare wires diameter: 11 mm
maximum output frequency
100 Hz
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Environment
Ambient air temp for storage/transportation
-40…65 °C
ip degree of protection
IP00
operating altitude
<= 1000 m without current derating
1000...3000 m with current derating 1 % per 100 m
ambient air temperature for operation
40…50 °C (with current derating 1.5 % per °C)
-10…40 °C (without current derating)
Environmental characteristics
3B1 conforming to IEC 721-3-3
3C2 conforming to IEC 721-3-3
3S1 conforming to IEC 721-3-3
relative humidity
0…95 %
vibration resistance
1 gn (f= 13…200 Hz) conforming to IEC 60068-2
1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2