Main
product specific application
Reduction of current harmonics
Complementary
electrical insulation class
Class F
[in] rated current
252 A for input
262 A for output
range compatibility
Altivar 61
Altivar Process ATV600
Altivar 71
Altivar Process ATV900
Product or component type
Passive filter
[us] rated supply voltage
400 V +/- 10 %
Cos phi
1 (150 % of line current)
0.85 (75 % of line current)
0.99 (100 % of line current)
thermal losses
1288 W
Efficiency
98 %
Max current
1.5 x nominal current (duration = 60 s)
Net weight
206 kg
Quantity per drive
1 filter per drive for variable speed drive ATV630 wall mount, motor: 110 kW/150 hp
1 filter per drive for variable speed drive ATV930 wall mount, motor: 110 kW/150 hp
2 filters per drive for variable speed drive ATV61H motor: 280 kW/450 hp
2 filters per drive for variable speed drive ATV71H motor: 280 kW/450 hp
2 filters per drive for variable speed drive ATV61Q motor: 280 kW/450 hp
thdi
5 % for variable speed drive ATV61H motor: 280 kW/450 hp
5 % for variable speed drive ATV71H motor: 280 kW/450 hp
5 % for variable speed drive ATV61Q motor: 280 kW/450 hp
5 % for variable speed drive ATV630 motor: 110 kW/150 hp
5 % for variable speed drive ATV930 motor: 110 kW/150 hp
electrical connection
A, B terminal, connection capacity: 2.5 mm²
X1-1...X2-3 terminal, connection capacity: 25...300 mm²
Network number of phases
3 phases
Power supply frequency
50 Hz +/- 2 %
Environment
Ambient air temp for storage/transportation
-25…55 °C storage in original packaging
-25…65 °C during transport
ip degree of protection
IP20
IP55 (enclosure mounting)
operating altitude
<= 1000 m without current derating
> 1000...4000 m with current derating 5 % per 1000 m
ambient air temperature for operation
45…60 °C (with current derating 3 % per °C)
5…45 °C (without current derating)
standards
G5/4 engineering recommendation
EN/IEC 61000-2-2
EN/IEC 61000-3-4
EN/IEC 61000-3-2
EN/IEC 61000-2-4
EN/IEC 61000-3-12
relative humidity
5…85 % without condensation
vibration resistance
2 mm peak to peak (f= 5…13.2 Hz) conforming to EN 60068-2-6
0.7 gn (f= 13.2…150 Hz) conforming to EN 60068-2-6