Main
product specific application
Radio interference input filter
Complementary
product compatibility
ATV212HD30M3X
ATV212HD55N4
ATV212HD75N4
ATV61HD30M3X
ATV61HD37M3X
ATV61HD45M3X
ATV61HD45N4
ATV61HD55N4
ATV61HD75N4
ATV71HD30M3X
ATV71HD37M3X
ATV71HD45M3X
ATV71HD45N4
ATV71HD55N4
ATV71HD75N4
ATV71WD45N4
ATV71WD55N4
ATV71WD75N4
[in] rated current
180 A
range compatibility
Altivar 61
Altivar 71
Altivar 212
Product or component type
EMC input filter
tightening torque
25 N.m
Maximum earth leakage current
140 mA at 400 V 50 Hz
193 mA at 480 V 60 Hz
80 mA at 400 V 50 Hz
86.3 mA at 480 V 60 Hz
thermal losses
18 W for ATV21HD55N4
34 W for ATV21HD75N4
23.1 W for ATV21HD30M3X
58 W for ATV61/ATV71 variable speed drives
Power supply voltage
380…500 V
200…240 V
Net weight
40 kg
Tolerance
10 %
electrical connection
Terminal 150 mm² 300 kcmil
Network number of phases
Three phase
Shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
Environment
Ambient air temp for storage/transportation
-40…65 °C
ip degree of protection
IP20
IP41 (upper part)
operating altitude
<= 1000 m without current derating
<= 1000 m without derating
1000...3000 m with current derating 1 % per 100 m
Range of product
Altivar
ambient air temperature for operation
-10…50 °C
standards
EN 133200
EN/IEC 61800-3
relative humidity
0…93 % conforming to IEC 68-2-3
vibration resistance
1 gn (f= 13…150 Hz) conforming to IEC 60068-2-6
1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6