Main
[ithe] thermal current under enclosure
16 A
Range
TeSys
Product Name
TeSys Mini-VARIO
performance level
Standard
Complementary
[icm] rated short circuit making capacity
0.5 kA at 400 V at Ipeak
[ie] rated operational current
11 A (AC-23) at 400 V
[ue] rated operational voltage
690 V AC 50/60 Hz
[ics] rated service breaking capacity
200 A at 400 V (AC-21A)
200 A at 400 V (AC-22A)
200 A at 400 V (AC-23A)
[icw] rated short-time withstand rms current
140 A at 400 V duration: 1 s
[ith] conventional thermal current
20 A
intermittent duty class
30
Product certifications
GL
UL
CSA
UKCA
Handle front plate colour
46.5 mm
Product or component type
Switch body
tightening torque
Power circuit: 0.7 N.m - on screw clamp terminals
[uimp] rated impulse withstand voltage
6 kV
Connections - terminals
Power circuit: screw clamp terminals4 mm² - solid
Power circuit: screw clamp terminals4 mm² - flexible - with cable end
Contacts type and composition
3 NO
rated operational power in w
11 kW at 690 V (AC-23A)
3 kW at 230...240 V (AC-3)
4 kW at 400...415 V (AC-3)
5.5 kW at 500 V (AC-3)
5.5 kW at 690 V (AC-3)
7.5 kW at 500 V (AC-23A)
4 kW at 230...240 V (AC-23A)
5.5 kW at 400...415 V (AC-23A)
width (w)
56 mm
mechanical robustness
Shocks 11 ms (15 gn) conforming to IEC 60068-2-27
Vibrations 10...150 Hz (1 gn) conforming to IEC 60068-2-6
network frequency
50/60 Hz
Net weight
0.11 kg
Mounting support
Symmetrical rail
depth
62 mm
mechanical durability
50000 cycles
electrical durability
30000 cycles DC-1...5
50000 cycles AC-21
Network type
AC
DC
Making capacity ( i rms)
200 A at 400 V AC-21A
200 A at 400 V AC-22A
200 A at 400 V AC-23A
Rated conditional short-circuit current
6 kA at 400 V - associated fuse 20 A aM
6 kA at 400 V - associated fuse 20 A gG
Suitability for isolation
Yes
Poles description
3P
Environment
ip degree of protection
IP20 conforming to IEC 60529
ambient air temperature for operation
-20…50 °C
standards
IEC 60947-3
fire resistance
960 °C conforming to IEC 60695-2-1
protective treatment
TC