Main
Device short name
VCFN
[ithe] thermal current under enclosure
20 A
Range
TeSys
Product Name
TeSys Mini-VARIO
performance level
Standard
Complementary
[ie] rated operational current
14.5 A (AC-23A) at 400 V
[ue] rated operational voltage
690 V AC
[icw] rated short-time withstand rms current
150 A at 400 V duration: 1 s
Control type
Rotary handle
Handle colour
Red
handle front plate dimension
60 x 60 mm
intermittent duty class
30
Handle front plate colour
Yellow
Product or component type
Emergency stop switch disconnector
[uimp] rated impulse withstand voltage
8 kV
marking
0 - 1
rated operational power in w
7.5 kW at 400 V (AC-23)
5.5 kW at 400 V (AC-3)
width (w)
82.5 mm
mechanical robustness
Vibrations 10...150 Hz (1 gn) conforming to IEC 60068-2-6
Shocks 11 ms (30 Gn) conforming to IEC 60068-2-27
Rotary handle padlocking
1 to 3 padlocks 4…8 mm
Net weight
0.512 kg
depth
106 mm
Making capacity ( i rms)
250 A at 400 V AC-21A
Rated conditional short-circuit current
10 kA at 400 V
Suitability for isolation
Yes
Poles description
3P
Environment
ambient air temperature for operation
-20…50 °C
standards
IEC 60947-4-1
fire resistance
960 °C conforming to IEC 60595-2-1
protective treatment
TC