Complementary
[icm] rated short circuit making capacity
0.5 kA at 400 V at Ipeak
[ie] rated operational current
8.1 A (AC-23) at 400 V
[ue] rated operational voltage
690 V AC 50/60 Hz
[ics] rated service breaking capacity
120 kA at 400 V (AC-21A)
120 kA at 400 V (AC-22A)
120 kA at 400 V (AC-23A)
[icw] rated short-time withstand rms current
140 A at 400 V duration: 1 s
[ith] conventional thermal current
12 A
Control type
Rotary handle
Handle colour
Red
handle front plate dimension
60 x 60 mm
intermittent duty class
30
Product certifications
GL
CCC
UL
CSA
UKCA
Handle front plate colour
Yellow
Product or component type
Emergency stop switch disconnector
tightening torque
Power circuit: 0.7 N.m - on screw clamp terminals
[uimp] rated impulse withstand voltage
6 kV
Device composition
Switch
Handle
Shaft extension
Connections - terminals
Power circuit: screw clamp terminals4 mm² - flexible - with cable end
Power circuit: screw clamp terminals4 mm² - solid
marking
0 - 1
Contacts type and composition
3 NO
Fixing mode
Hole with 22.5 mm for handle
By clips for switch
rated operational power in w
3 kW at 230...240 V (AC-23A)
4 kW at 400...415 V (AC-23A)
5.5 kW at 500 V (AC-23A)
7.5 kW at 690 V (AC-23A)
1.5 kW at 230...240 V (AC-3)
3 kW at 400...415 V (AC-3)
4 kW at 500 V (AC-3)
4 kW at 690 V (AC-3)
width (w)
60 mm
mechanical robustness
Vibrations 10...150 Hz (5 gn) conforming to IEC 60068-2-6
Shocks 11 ms (15 gn) conforming to IEC 60068-2-27
Rotary handle padlocking
1 to 3 padlocks 4…8 mm
Net weight
0.334 kg
Mounting support
Handle: door
Switch: symmetrical rail
mechanical durability
50000 cycles
electrical durability
30000 cycles DC-1...5
50000 cycles AC-21
Network type
AC
DC
Making capacity ( i rms)
120 A at 400 V AC-21A
120 A at 400 V AC-22A
120 A at 400 V AC-23A
rotary handle mounting style
Extended
Rated conditional short-circuit current
6 kA at 400 V - associated fuse 12 A aM
6 kA at 400 V - associated fuse 12 A gG
Suitability for isolation
Yes
Poles description
3P