Complementary
[icm] rated short circuit making capacity
2.8 kA at 400 V at Ipeak
[ie] rated operational current
68.5 A AC-23 Ue: 400 V
[ue] rated operational voltage
690 V AC 50/60 Hz
compatibility code
Main switch disconnector
[ics] rated service breaking capacity
1000 A at 400 V (AC-21A)
1000 A at 400 V (AC-22A)
1000 A at 400 V (AC-23A)
[icw] rated short time withstand current
1500 A at 400 V duration: 1 s
[ith] conventional thermal current
125 A
Base dimension
90 x 90 mm
Control type
Rotary handle
Handle colour
Black
intermittent duty class
30
Product certifications
CCC
UL
CSA
GL
UKCA
Handle front plate colour
Yellow
tightening torque
Power circuit: 22.6 N.m - on screw clamp terminals
[uimp] rated impulse withstand voltage
8 kV
Device composition
Switch
Handle
product weight
1.2 kg
marking
0 - 1
Device application
Preventive maintenance
width (w)
90 mm
mechanical robustness
Vibrations 10...150 Hz (1 gn) conforming to IEC 60068-2-6
Shocks 11 ms (30 Gn) conforming to IEC 60068-2-27
Rotary handle padlocking
1 to 3 padlocks 4…8 mm
Iec rated operational power in w
22 kW at 230...240 V (AC-3)
30 kW at 400...415 V (AC-3)
30 kW at 690 V (AC-3)
37 kW at 500 V (AC-3)
37 kW at 690 V (AC-23A)
45 kW at 500 V (AC-23A)
22 kW at 230...240 V (AC-23A)
37 kW at 400...415 V (AC-23A)
Iec terminal connection
Power circuit: screw clamp terminals95 mm² - solid
Power circuit: screw clamp terminals70 mm² - flexible - with cable end
Mounting support
Handle: door
Switch: door
mechanical durability
30000 cycles
electrical durability
30000 cycles AC-21
30000 cycles DC-1...5
Network type
AC
DC
Making capacity ( i rms)
1250 A at 400 V AC-21A
1250 A at 400 V AC-22A
1250 A at 400 V AC-23A
mounting method
By 4 screws for handle
Rated conditional short circuit current
10 kA at 400 V - associated fuse 125 A aM
10 kA at 400 V - associated fuse 125 A gG
rotary handle mounting style
Direct
contact type and composition
3 NO
Suitability for isolation
Yes
Poles description
3P