Main
Analogue i/o processor capacity
24 I/O
Number of application specific channel
8
Complementary
Application structure
1 master task
1 fast task
32 event tasks
Product certifications
DNV
GL
RMRS
BV
ABS
LR
RINA
Product or component type
Single-format PL7 processor
Current consumption
440 mA at 5 V DC
Communication module processor capacity
1 network module
2 AS-Interface bus modules
1 CANopen
Discrete i/o processor capacity
512 I/O
marking
CE
Number of slots
16
32
24
Local signalling
1 LED (green) for processor running (RUN)
1 LED (red) for I/O module or configuration fault (I/O)
1 LED (red) for processor or system fault (ERR)
1 LED (yellow) for activity on the terminal port (TER)
Memory description
Internal RAM (with PCMCIA card) 32 Kwords data
Internal RAM (without PCMCIA card) 32 Kwords program and data
PCMCIA card 128 Kwords additional data storage
PCMCIA card 64 Kwords program
Net weight
0.38 kg
number of instructions per ms
0.85 Kinst/ms 65 % Boolean + 35 % fixed arithmetic with PCMCIA card
1.05 Kinst/ms 65 % Boolean + 35 % fixed arithmetic without PCMCIA card
1.18 Kinst/ms 100 % Boolean with PCMCIA card
1.52 Kinst/ms 100 % Boolean without PCMCIA card
Maximum size of object areas
30.5 %MWi internal words located internal data
32 %KWi constant words located internal data
4096 %Mi located internal bits
Integrated connection type
Non isolated serial link 2 female mini DIN connector (19.2 kbit/s)
Module format
Standard
Number of racks
2 12 slots
4 4/6/8 slots
Pollution degree
2
execution time per instruction
0.5 µs Boolean without PCMCIA card
0.6 µs Boolean with PCMCIA card
0.62 µs word or fixed-point arithmetic without PCMCIA card
0.87 µs word or fixed-point arithmetic with PCMCIA card
44 µs floating points with PCMCIA card
44 µs floating points without PCMCIA card
System overhead
0.8 ms for fast task
1.5 ms for master task
Software designation
PL7 Junior/Pro
Environment
Ambient air temp for storage/transportation
-25…70 °C
ip degree of protection
IP20
operating altitude
0...2000 m
Range of product
Modicon Premium Automation platform
ambient air temperature for operation
0…60 °C
standards
CSA C22.2 No 213 Class I Division 2 Group A
CSA C22.2 No 142
89/336/EEC
UL 508
73/23/EEC
CSA C22.2 No 213 Class I Division 2 Group C
92/31/EEC
93/68/EEC
CSA C22.2 No 213 Class I Division 2 Group B
IEC 61131-2
CSA C22.2 No 213 Class I Division 2 Group D
relative humidity
10…95 % without condensation for operation
5…95 % without condensation for storage
protective treatment
TC