Main
reverse polarity protection
Reverse mounted diode
Complementary
product compatibility
Dial and Power
[ures] residual voltage
1.5 V
Product certifications
RINA
DNV
BV
ABS
GL
RMRS
LR
response time
1.2 ms
maximum leakage current
0.1 mA, at 30 V
Product or component type
Discrete output module
Current consumption
155 mA at 5 V DC
current per channel
0.1 A
marking
CE
Isalotion resistance
> 10 MOhm 500 V
Maximum current per module
5 A
Net weight
0.36 kg
Discrete output type
Solid state protected
Discrete output voltage
24 V DC positive conforming to EN/IEC 61131-2 19...30 V
Discrete output number
64
Minimum load impedance
220 W at state 1
Power dissipation
(2,4 W + 0,1 W x nombre de sorties)
Module format
Standard
Output overload protection
Automatic trip
Paralleling of outputs
Yes : 3 maximum
Pollution degree
2
electrical connection
4 connectors HE-10
Maximum tungsten load
1.2 W
dielectric strength
1500 V 50/60 Hz 60 s
Output overvoltage protection
By transil diode
Short-circuit protection
Automatic trip
Environment
Ambient air temp for storage/transportation
-25…70 °C
ip degree of protection
IP20
operating altitude
0...2000 m
Range of product
Modicon Premium Automation platform
ambient air temperature for operation
0…60 °C
standards
UL 508
CSA C22.2 No 213 Class I Division 2 Group A
CSA C22.2 No 213 Class I Division 2 Group C
93/68/EEC
89/336/EEC
IEC 61131-2
CSA C22.2 No 142
CSA C22.2 No 213 Class I Division 2 Group B
92/31/EEC
CSA C22.2 No 213 Class I Division 2 Group D
73/23/EEC
relative humidity
10…95 % without condensation for operation
5…95 % without condensation for storage
protective treatment
TC