Main
reverse polarity protection
Reverse mounted diode
Complementary
[ures] residual voltage
1.2 V
Product certifications
DNV
RMRS
GL
BV
ABS
RINA
LR
response time
1.2 ms
maximum leakage current
0.5 mA at state 0
Product or component type
Discrete output module
Current consumption
80 mA at 5 V DC
current per channel
0.625 A
marking
CE
Discrete output current
0.5 A
switching frequency
0.5/LI² Hz
Isalotion resistance
> 10 MOhm 500 V
Maximum current per module
7 A
Net weight
0.34 kg
Discrete output type
Solid state protected
Discrete output voltage
24 V DC positive conforming to EN/IEC 61131-2 19...30 V
Discrete output number
16
Minimum load impedance
48 W
Power dissipation
(1.1 W + 0.75 W x No of outputs x current per module)
Module format
Standard
Output overload protection
Electronic tripping on reactivation
Pollution degree
2
electrical connection
Screw terminal block
dielectric strength
1500 V 50/60 Hz 60 s
Output overvoltage protection
By transil diode
Preactuator voltage detection threshold
16 V
Short-circuit protection
Electronic tripping on reactivation
Environment
Ambient air temp for storage/transportation
-25…70 °C
ip degree of protection
IP20
operating altitude
0...2000 m
Range of product
Modicon Premium Automation platform
ambient air temperature for operation
0…60 °C
standards
CSA C22.2 No 213 Class I Division 2 Group C
CSA C22.2 No 142
93/68/EEC
CSA C22.2 No 213 Class I Division 2 Group D
89/336/EEC
CSA C22.2 No 213 Class I Division 2 Group A
UL 508
IEC 61131-2
CSA C22.2 No 213 Class I Division 2 Group B
73/23/EEC
92/31/EEC
relative humidity
10…95 % without condensation for operation
5…95 % without condensation for storage
protective treatment
TC