SPECIFICATIONS
Main
Analogue input resolution 14 bits
Cross talk 80 dB
Complementary
Absolute accuracy error +/- 0.5 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe
+/- 0.2 % of full scale at 25 °C for thermocouple K - 200...1300 °C
+/- 0.2 % of full scale at 25 °C for thermocouple J - 200...1000 °C
+/- 0.2 % of full scale at 25 °C for thermocouple E - 200...800 °C
+/- 0.2 % of full scale at 25 °C for thermocouple T - 200...400 °C
+/- 0.2 % of full scale at 25 °C for thermocouple N - 200...1300 °C
+/- 0.2 % of full scale at 25 °C for thermocouple B 250...400 °C
+/- 0.1 % of full scale at 25 °C for thermocouple B 400...1280 °C
+/- 0.2 % of full scale at 25 °C for thermocouple R, S 0...1760°C
product compatibility Modicon M241C
Handle front plate colour 50 mm
Product or component type Analogue input cartridge
Analogue input number 2
Analogue input type thermocouple - 200...1000 °C with thermocouple J
thermocouple - 200...1300 °C with thermocouple K
thermocouple 0...1760 °C with thermocouple R
thermocouple 0...1760 °C with thermocouple S
thermocouple 0...1820 °C with thermocouple B
thermocouple - 200...400 °C with thermocouple T
thermocouple - 200...1300 °C with thermocouple N
thermocouple - 200...800 °C with thermocouple E
Ni 100/Ni 1000 temperature probe - 60...180 °C
Pt 100 temperature probe - 200...850 °C
Pt 1000 temperature probe - 200...600 °C
width (w) 34 mm
supply voltage limits 20.4…28.8 V
Local signalling 1 LED (green) for PWR
temperature drift +/- 0.008 %FS/°C
Net weight 0.055 kg
Maximum cable distance between devices Twisted shielded pairs cable: <30 m for input
Immunity to microbreaks 10 ms
input impedance >= 1 MOhm
depth 21 mm
repeat accuracy +/- 0.1 %FS
electrical connection 1 x 1.5 mm² 1 spring terminal block with pitch 3.81 mm adjustment for outputs and supply
Non-linearity +/- 0.05 %FS
Permissible continuous overload 6 V
Insulation Between input and internal logic at 500 V DC
Non-insulated between inputs
Lsb value 0.1 °C
Sampling duration 100 ms
Type of cable Twisted shielded pairs cable