SPECIFICATIONS
Main
Discrete input voltage type DC
Discrete input current 4.4 mA
Discrete output voltage type DC
Input/output number of block 16 I/O
Complementary
[ue] rated operational voltage 24 V DC
range compatibility Modicon LMC058
Modicon M258
Product certifications GOST-R
C-Tick
ATEX II 3g EEx nA II T5
cURus
Product or component type CANopen interface I/O block
Bus type CANopen
marking CE
Enclosure material Plastic
Discrete output current <= 0.5 A
Fixing mode By 2 screws
Discrete input logic Positive
Discrete input voltage 24 V
Local signalling 2 LEDs for bus diagnostic
1 LED for actuator power supply diagnostics
1 LED for sensor power supply diagnostics
Discrete input number 0…16 configurable by software
Disturbance radiated/conducted CISPR 11
Net weight 0.32 kg
Discrete output type Transistor
Discrete output voltage 24 V
Operating position Any position
Discrete output number 0…16 output(s) configurable by software
Pollution degree 2 conforming to IEC 60664
electrical connection 1 male connector M12 - A coding - 5 ways for CANopen bus IN
1 female connector M12 - B coding - 4 ways for TM7 bus OUT
1 male connector M8 - 4 ways for power IN
1 female connector M8 - 4 ways for power OUT
1 female connector M12 - A coding - 5 ways for CANopen bus OUT
16 female connectors M8 - 3 ways for sensor or actuator
Sensor power supply 24 V, 500 mA for all channels with overload, short-circuit and reverse polarity protection
Input/output number 16
Resistance to electrostatic discharge 6 kV in contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to EN/IEC 61000-4-2
Shock resistance 30 gn for 11 ms conforming to IEC 60721-3-5 Class 5M3
Resistance to electromagnetic fields 10 V/m 0.08…2 Hz conforming to EN/IEC 61000-4-3
1 V/m 2…2.7 Hz conforming to EN/IEC 61000-4-3
Environment
Ambient air temp for storage/transportation -25…85 °C
ip degree of protection IP67 conforming to IEC 61131-2
operating altitude 0...2000 m
Range of product Modicon TM7
ambient air temperature for operation -10…60 °C
electromagnetic compatibility EN/IEC 61000-4-6
standards IEC 61131-2
Storage altitude 0…3000 m
relative humidity 5…95 % without condensation or dripping water
Surge withstand for dc 24 v circuit 1 kV power supply (common mode) conforming to EN/IEC 61000-4-5
0.5 kV power supply (differential mode) conforming to EN/IEC 61000-4-5
1 kV unshielded links (common mode) conforming to EN/IEC 61000-4-5
0.5 kV unshielded links (differential mode) conforming to EN/IEC 61000-4-5
1 kV shielded links (common mode) conforming to EN/IEC 61000-4-5
0.5 kV shielded links (differential mode) conforming to EN/IEC 61000-4-5
vibration resistance 7.5 mm constant amplitude (f= 2…8 Hz) conforming to IEC 60721-3-5 Class 5M3
2 gn constant acceleration (f= 8…200 Hz) conforming to IEC 60721-3-5 Class 5M3
4 gn constant acceleration (f= 200…500 Hz) conforming to IEC 60721-3-5 Class 5M3
resistance to fast transients 2 kV (power supply) conforming to EN/IEC 61000-4-4
1 kV (input/output) conforming to EN/IEC 61000-4-4
1 kV (shielded cable) conforming to EN/IEC 61000-4-4