Main
Input/output number of block
4 O
Complementary
[ue] rated operational voltage
24 V DC
range compatibility
Modicon LMC058
Modicon M258
Analogue output resolution
12 bits
Product certifications
C-Tick
GOST-R
cURus
ATEX II 3g EEx nA II T5
Analogue output range
0...20 mA
Product or component type
Analog I/O expansion block
Bus type
TM7 bus
marking
CE
Enclosure material
Plastic
Fixing mode
By 2 screws
Analogue output number
4
Analogue output type
Current
Local signalling
2 LEDs for bus diagnostic
2 LEDs for sensor/actuator power supply status
Disturbance radiated/conducted
CISPR 11
Net weight
0.2 kg
Operating position
Any position
Pollution degree
2 conforming to IEC 60664
electrical connection
1 male connector M12 - B coding - 4 ways for bus IN
1 female connector M12 - B coding - 4 ways for bus OUT
1 male connector M8 - 4 ways for power IN
1 female connector M8 - 4 ways for power OUT
4 female connectors M12 - A coding - 5 ways for actuator
Sensor power supply
24 V, 500 mA for all channels with overload, short-circuit and reverse polarity protection
Input/output number
4
Resistance to electrostatic discharge
6 kV in contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to EN/IEC 61000-4-2
Shock resistance
30 gn for 11 ms conforming to IEC 60721-3-5 Class 5M3
Resistance to electromagnetic fields
10 V/m 0.08…2 Hz conforming to EN/IEC 61000-4-3
1 V/m 2…2.7 Hz conforming to EN/IEC 61000-4-3
Environment
Ambient air temp for storage/transportation
-25…85 °C
ip degree of protection
IP67 conforming to IEC 61131-2
operating altitude
0...2000 m
Range of product
Modicon TM7
ambient air temperature for operation
-10…60 °C
electromagnetic compatibility
EN/IEC 61000-4-6
standards
IEC 61131-2
Storage altitude
0…3000 m
relative humidity
5…95 % without condensation or dripping water
Surge withstand for dc 24 v circuit
1 kV power supply (common mode) conforming to EN/IEC 61000-4-5
0.5 kV power supply (differential mode) conforming to EN/IEC 61000-4-5
1 kV unshielded links (common mode) conforming to EN/IEC 61000-4-5
0.5 kV unshielded links (differential mode) conforming to EN/IEC 61000-4-5
1 kV shielded links (common mode) conforming to EN/IEC 61000-4-5
0.5 kV shielded links (differential mode) conforming to EN/IEC 61000-4-5
vibration resistance
7.5 mm constant amplitude (f= 2…8 Hz) conforming to IEC 60721-3-5 Class 5M3
2 gn constant acceleration (f= 8…200 Hz) conforming to IEC 60721-3-5 Class 5M3
4 gn constant acceleration (f= 200…500 Hz) conforming to IEC 60721-3-5 Class 5M3
resistance to fast transients
2 kV (power supply) conforming to EN/IEC 61000-4-4
1 kV (input/output) conforming to EN/IEC 61000-4-4
1 kV (shielded cable) conforming to EN/IEC 61000-4-4