Main
Encoder type
1 incremental encoder
Discrete input current
3.3 mA at 24 V
product specific application
Downcounting
Frequency generator
Upcounting
Period measurement
Frequency meter
Axis following with encoder
Complementary
product compatibility
Logic controller
Motion controller
range compatibility
Modicon LMC058
Modicon M258
Product certifications
CSA
C-Tick
GOST-R
cULus
Counter inputs resolution
16 bits/32 bits
Product or component type
Counter module
Current consumption
2 mA at 5 V DC bus
58 mA at 24 V DC input/output
marking
CE
maximum power dissipation in w
1.41 W
Function of module
2 x 24 V DC auxiliary inputs
24 V DC encoder power supply
Discrete input logic
Sink
Input resistance
7.19 kOhm
isolation
500 Vrms AC insulation between channel and bus
Discrete input voltage
24 V DC
Discrete input number
1
Disturbance radiated/conducted
CISPR 11
Net weight
0.025 kg
counting frequency
100 kHz
Maximum cycle time
2 ms
Pollution degree
2 conforming to IEC 60664
Input compatibility
1 incremental encoder (24 V)
Resistance to electrostatic discharge
4 kV on contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to EN/IEC 61000-4-2
Shock resistance
15 gn for 11 ms
Resistance to electromagnetic fields
1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
Surge withstand
0.5 kV differential mode conforming to EN/IEC 61000-4-5
1 kV common mode conforming to EN/IEC 61000-4-5
Environment
Ambient air temp for storage/transportation
-25…70 °C
ip degree of protection
IP20 conforming to IEC 61131-2
operating altitude
0...2000 m
Range of product
Modicon TM5
ambient air temperature for operation
0…55 °C without derating (horizontal installation)
0…60 °C with derating factor (horizontal installation)
0…50 °C (vertical installation)
electromagnetic compatibility
EN/IEC 61000-4-6
standards
IEC 61131-2
CSA C22.2 No 213
CSA C22.2 No 142
UL 508
Storage altitude
0…3000 m
relative humidity
5…95 % without condensation
vibration resistance
1 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on DIN rail
resistance to fast transients
1 kV (I/O) conforming to EN/IEC 61000-4-4
1 kV (shielded cable) conforming to EN/IEC 61000-4-4
2 kV (power lines) conforming to EN/IEC 61000-4-4