Main
Discrete output logic
Source
Complementary
product compatibility
Logic controller
PacDrive LMC Pro
PacDrive LMC Pro 2
PacDrive LMC Eco
Motion controller
range compatibility
PacDrive LMC motion controller
Modicon LMC058
Modicon M258
Product certifications
cULus
CSA
C-Tick
GOST-R
response time
<= 300 µs from state 0 to state 1 for output
<= 300 µs from state 1 to state 0 for output
maximum leakage current
5 µA when switched off
Product or component type
Discrete output module
Current consumption
36 mA at 5 V DC bus
30 mA at 24 V DC input/output
maximum voltage drop
<0.3 V at 500 mA for output
<2 V at 500 mA for sensor supply
current per channel
0.5 A
marking
CE
maximum power dissipation in w
1.2 W
output voltage
24 V DC
isolation
500 Vrms AC insulation between channel and bus
No insulation between channels
Maximum current per output common
3 A
switching frequency
<= 500 Hz resistive load
Colour
White
Local signalling
1 LED green for power supply
1 LED red for power supply
6 LEDs yellow for output status
Net weight
0.025 kg
Discrete output type
Transistor
Discrete output number
6
Maximum supply current for sensors
500 mA
output voltage limits
20.4...28.8 V
Pollution degree
2 conforming to IEC 60664
electrical connection
2 wires
Peak output current
12 A
Shock resistance
15 gn for 11 ms
Protection type
Short-circuit protection
Overload protection
Reverse polarity protection
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 61131-2
operating altitude
0...2000 m
Range of product
Modicon TM5
ambient air temperature for operation
-10…55 °C without derating (horizontal installation)
-10…60 °C with derating factor (horizontal installation)
-10…50 °C (vertical installation)
electromagnetic compatibility
Electrostatic discharge immunity test, 4 kV on contact conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test, 8 kV in air conforming to EN/IEC 61000-4-2
Susceptibility to electromagnetic fields, 1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
Electrical fast transient/burst immunity test, 1 kV I/O conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test, 1 kV shielded cable conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test, 2 kV power lines conforming to EN/IEC 61000-4-4
1.2/50 µs shock waves immunity test, 0.5 kV differential mode conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test, 1 kV common mode conforming to EN/IEC 61000-4-5
Conducted RF disturbances conforming to EN/IEC 61000-4-6
Conducted and radiated emissions conforming to CISPR 11
standards
UL 508
CSA C22.2 No 213
IEC 61131-2
CSA C22.2 No 142
Storage altitude
0…3000 m
relative humidity
5…95 % without condensation
vibration resistance
1 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on DIN rail