Main
Discrete output logic
Source
Complementary
product compatibility
PacDrive LMC Pro
Motion controller
PacDrive LMC Pro 2
PacDrive LMC Eco
Logic controller
range compatibility
Modicon LMC058
PacDrive LMC motion controller
Modicon M258
Product certifications
CSA
cULus
C-Tick
GOST-R
response time
<= 300 µs from state 0 to state 1 for output
<= 300 µs from state 1 to state 0 for output
maximum leakage current
5 µA when switched off
Product or component type
Discrete output module
Current consumption
56 mA at 5 V DC bus
40 mA at 24 V DC input/output
maximum voltage drop
<2 V at 500 mA for sensor supply
<0.1 V at 500 mA for output
current per channel
0.5 A
marking
CE
output voltage
24 V DC
isolation
No insulation between channels
500 Vrms AC insulation between channel and bus
Maximum current per output common
8 A
switching frequency
<= 500 Hz resistive load
Colour
White
Local signalling
1 LED green/red for power supply
16 LEDs yellow for output status
Net weight
0.025 kg
Discrete output type
Transistor
Discrete output number
16
Maximum supply current for sensors
500 mA
output voltage limits
20.4...28.8 V
Pollution degree
2 conforming to IEC 60664
electrical connection
1 wire
Peak output current
3 A
Shock resistance
15 gn for 11 ms
Protection type
Reverse polarity protection
Overload protection
Short-circuit protection
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 61131-2
operating altitude
0...2000 m
Range of product
Modicon TM5
ambient air temperature for operation
-10…55 °C without derating (horizontal installation)
-10…60 °C with derating factor (horizontal installation)
-10…50 °C (vertical installation)
electromagnetic compatibility
Electrostatic discharge immunity test, 4 kV on contact conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test, 8 kV in air conforming to EN/IEC 61000-4-2
Susceptibility to electromagnetic fields, 1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
Electrical fast transient/burst immunity test, 1 kV I/O conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test, 1 kV shielded cable conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test, 2 kV power lines conforming to EN/IEC 61000-4-4
1.2/50 µs shock waves immunity test, 0.5 kV differential mode conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test, 1 kV common mode conforming to EN/IEC 61000-4-5
Conducted RF disturbances conforming to EN/IEC 61000-4-6
Conducted and radiated emissions conforming to CISPR 11
standards
IEC 61131-2
UL 508
CSA C22.2 No 213
CSA C22.2 No 142
Storage altitude
0…3000 m
relative humidity
5…95 % without condensation
vibration resistance
1 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on DIN rail