Main
Discrete output logic
Source
Complementary
product compatibility
PacDrive LMC Eco
PacDrive LMC Pro 2
PacDrive LMC Pro
Motion controller
Logic controller
range compatibility
PacDrive LMC motion controller
Modicon LMC058
Modicon M258
Product certifications
GOST-R
CSA
cULus
C-Tick
response time
<= 300 µs from state 0 to state 1 for output
<= 300 µs from state 1 to state 0 for output
maximum leakage current
5 µA when switched off
Product or component type
Discrete output module
Current consumption
52 mA at 5 V DC bus
48 mA at 24 V DC input/output
maximum voltage drop
<0.3 V at 500 mA for output
<2 V at 500 mA for sensor supply
current per channel
0.5 A
marking
CE
maximum power dissipation in w
2.04 W
output voltage
24 V DC
isolation
500 Vrms AC insulation between channel and bus
No insulation between channels
Maximum current per output common
6 A
switching frequency
<= 500 Hz resistive load
Colour
White
Local signalling
1 LED green for power supply
1 LED red for power supply
12 LEDs yellow for output status
Net weight
0.025 kg
Discrete output type
Transistor
Discrete output number
12
Maximum supply current for sensors
500 mA
output voltage limits
20.4...28.8 V
Pollution degree
2 conforming to IEC 60664
electrical connection
1 wire
Peak output current
12 A
Shock resistance
15 gn for 11 ms
Protection type
Reverse polarity protection
Overload protection
Short-circuit protection
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 61131-2
operating altitude
0...2000 m
Range of product
Modicon TM5
ambient air temperature for operation
-10…55 °C without derating (horizontal installation)
-10…60 °C with derating factor (horizontal installation)
-10…50 °C (vertical installation)
electromagnetic compatibility
Electrostatic discharge immunity test, 4 kV on contact conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test, 8 kV in air conforming to EN/IEC 61000-4-2
Susceptibility to electromagnetic fields, 1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
Electrical fast transient/burst immunity test, 1 kV I/O conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test, 1 kV shielded cable conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test, 2 kV power lines conforming to EN/IEC 61000-4-4
1.2/50 µs shock waves immunity test, 0.5 kV differential mode conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test, 1 kV common mode conforming to EN/IEC 61000-4-5
Conducted RF disturbances conforming to EN/IEC 61000-4-6
Conducted and radiated emissions conforming to CISPR 11
standards
CSA C22.2 No 213
UL 508
CSA C22.2 No 142
IEC 61131-2
Storage altitude
0…3000 m
relative humidity
5…95 % without condensation
vibration resistance
1 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on DIN rail