Default
Series
Modicon TM5
Main
Discrete input voltage type
DC
Discrete input current
3.75 mA
Complementary
product compatibility
Logic controller
Motion controller
PacDrive LMC Pro
PacDrive LMC Eco
PacDrive LMC Pro 2
range compatibility
Modicon M258
PacDrive LMC motion controller
Modicon LMC058
Product certifications
CSA
C-Tick
cULus
GOST-R
Product or component type
Discrete input module
Current consumption
28 mA at 5 V DC bus
25 mA at 24 V DC all inputs On
maximum voltage drop
<2 V at 500 mA for sensor supply
marking
CE
maximum power dissipation in w
0.73 W
Discrete input logic
Sink
input voltage limits
20.4...28.8 V
isolation
No insulation between channels
500 Vrms AC insulation between channel and bus
Colour
White
Discrete input voltage
24 V
Local signalling
1 LED green for power supply
1 LED red for power supply
4 LEDs green for input status
Discrete input number
4
Net weight
0.025 kg
voltage state 1 guaranteed
>= 15 V
Input filtering
<= 25 ms configurable by software
<= 100 ms hardware
input impedance
6.4 kOhm
Maximum supply current for sensors
500 mA
voltage state 0 guaranteed
<= 5 V
Pollution degree
2 conforming to IEC 60664
electrical connection
3 wires
Shock resistance
15 gn for 11 ms
Protection type
Short-circuit protection
Overload protection
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 61131-2
operating altitude
0...2000 m
Range of product
Modicon TM5
ambient air temperature for operation
-10…55 °C without derating (horizontal installation)
-10…60 °C with derating factor (horizontal installation)
-10…50 °C (vertical installation)
electromagnetic compatibility
Electrostatic discharge immunity test, 4 kV on contact conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test, 8 kV in air conforming to EN/IEC 61000-4-2
Susceptibility to electromagnetic fields, 1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
Electrical fast transient/burst immunity test, 1 kV I/O conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test, 1 kV shielded cable conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test, 2 kV power lines conforming to EN/IEC 61000-4-4
1.2/50 µs shock waves immunity test, 0.5 kV differential mode conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test, 1 kV common mode conforming to EN/IEC 61000-4-5
Conducted RF disturbances conforming to EN/IEC 61000-4-6
Conducted and radiated emissions conforming to CISPR 11
standards
IEC 61131-2
CSA C22.2 No 142
UL 508
CSA C22.2 No 213
Storage altitude
0…3000 m
relative humidity
5…95 % without condensation
vibration resistance
1 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on DIN rail