Main
Discrete input voltage type
AC
Discrete input current
5…11 mA
Complementary
product compatibility
PacDrive LMC Pro
Logic controller
PacDrive LMC Pro 2
Motion controller
PacDrive LMC Eco
range compatibility
Modicon M258
Modicon LMC058
PacDrive LMC motion controller
Product certifications
cULus
CSA
GOST-R
C-Tick
Product or component type
Discrete input module
Current consumption
34 mA at 5 V DC bus
marking
CE
maximum power dissipation in w
1.08 W
input voltage limits
100...240 V
isolation
No insulation between channels
2500 V AC insulation between channel and bus for 1 minute
Colour
Black
Discrete input voltage
100...240 V
Local signalling
1 LED green for power supply
1 LED red for power supply
4 LEDs green for input status
Discrete input number
4
Net weight
0.025 kg
Input filtering
<= 25 ms configurable by software
<= 30 ms hardware from state 1 to state 0
<= 40 ms hardware from state 0 to state 1
Pollution degree
2 conforming to IEC 60664
electrical connection
2 wires
Shock resistance
15 gn for 11 ms
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 61131-2
operating altitude
0...2000 m
Range of product
Modicon TM5
ambient air temperature for operation
-10…55 °C without derating (horizontal installation)
-10…60 °C with derating factor (horizontal installation)
-10…50 °C (vertical installation)
electromagnetic compatibility
Electrostatic discharge immunity test, 4 kV on contact conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test, 8 kV in air conforming to EN/IEC 61000-4-2
Susceptibility to electromagnetic fields, 1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
Electrical fast transient/burst immunity test, 1 kV I/O conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test, 1 kV shielded cable conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test, 2 kV power lines conforming to EN/IEC 61000-4-4
1.2/50 µs shock waves immunity test, 0.5 kV differential mode conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test, 1 kV common mode conforming to EN/IEC 61000-4-5
Conducted RF disturbances conforming to EN/IEC 61000-4-6
Conducted and radiated emissions conforming to CISPR 11
standards
UL 508
CSA C22.2 No 142
IEC 61131-2
CSA C22.2 No 213
Storage altitude
0…3000 m
relative humidity
5…95 % without condensation
vibration resistance
1 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on DIN rail