SPECIFICATIONS
Main
Discrete input voltage type DC
Discrete input current 3.75 mA
Complementary
product compatibility Motion controller
PacDrive LMC Pro
PacDrive LMC Pro 2
Logic controller
PacDrive LMC Eco
range compatibility PacDrive LMC motion controller
Modicon M258
Modicon LMC058
Product certifications cULus
C-Tick
GOST-R
CSA
Product or component type Discrete input module
Current consumption 36 mA at 5 V DC bus
73 mA at 24 V DC all inputs On
marking CE
maximum power dissipation in w 1.93 W
Discrete input logic Sink
input voltage limits 20.4...28.8 V
isolation 500 Vrms AC insulation between channel and bus
No insulation between channels
Colour White
Discrete input voltage 24 V
Local signalling 1 LED green for power supply
1 LED red for power supply
12 LEDs green for input status
Discrete input number 12
Net weight 0.025 kg
voltage state 1 guaranteed >= 15 V
Input filtering <= 25 ms configurable by software
<= 100 ms hardware
input impedance 6.4 kOhm
voltage state 0 guaranteed <= 5 V
Pollution degree 2 conforming to IEC 60664
electrical connection 1 wire
Shock resistance 15 gn for 11 ms
Environment
Ambient air temp for storage/transportation -40…70 °C
ip degree of protection IP20 conforming to IEC 61131-2
operating altitude 0...2000 m
Range of product Modicon TM5
ambient air temperature for operation -10…55 °C without derating (horizontal installation)
-10…60 °C with derating factor (horizontal installation)
-10…50 °C (vertical installation)
electromagnetic compatibility Electrostatic discharge immunity test, 4 kV on contact conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test, 8 kV in air conforming to EN/IEC 61000-4-2
Susceptibility to electromagnetic fields, 1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
Electrical fast transient/burst immunity test, 1 kV I/O conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test, 1 kV shielded cable conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test, 2 kV power lines conforming to EN/IEC 61000-4-4
1.2/50 µs shock waves immunity test, 0.5 kV differential mode conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test, 1 kV common mode conforming to EN/IEC 61000-4-5
Conducted RF disturbances conforming to EN/IEC 61000-4-6
Conducted and radiated emissions conforming to CISPR 11
standards CSA C22.2 No 213
IEC 61131-2
UL 508
CSA C22.2 No 142
Storage altitude 0…3000 m
relative humidity 5…95 % without condensation
vibration resistance 1 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on DIN rail