Main
product specific application
Communication between remote I/O
Distribute power to TM5 bus and I/O
Complementary
product compatibility
Logic controller
Motion controller
range compatibility
Modicon M258
Modicon LMC058
Product certifications
CSA
cULus
C-Tick
GOST-R
Product or component type
Remote receiver module
Current consumption
25 mA at 24 V DC input/output
bus length
2500 m
marking
CE
maximum power dissipation in w
2.22 W
Colour
Grey
Local signalling
1 LED green for power supply
1 LED red for power bus current
1 LED red for power supply
1 LED yellow for communication data bus
Disturbance radiated/conducted
CISPR 11
Net weight
0.025 kg
Maximum cable distance between devices
100 m
Pollution degree
2 conforming to IEC 60664
Resistance to electrostatic discharge
4 kV on contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to EN/IEC 61000-4-2
Shock resistance
15 gn for 11 ms
Resistance to electromagnetic fields
1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
Surge withstand
0.5 kV differential mode conforming to EN/IEC 61000-4-5
1 kV common mode conforming to EN/IEC 61000-4-5
Environment
Ambient air temp for storage/transportation
-25…70 °C
ip degree of protection
IP20 conforming to IEC 61131-2
IP67
operating altitude
0...2000 m
Range of product
Modicon TM5
ambient air temperature for operation
0…50 °C (vertical installation)
0…55 °C without derating (horizontal installation)
0…60 °C with derating factor (horizontal installation)
electromagnetic compatibility
EN/IEC 61000-4-6
standards
CSA C22.2 No 142
CSA C22.2 No 213
IEC 61131-2
UL 508
Storage altitude
0…3000 m
relative humidity
5…95 % without condensation
vibration resistance
1 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on DIN rail
resistance to fast transients
1 kV (I/O) conforming to EN/IEC 61000-4-4
1 kV (shielded cable) conforming to EN/IEC 61000-4-4
2 kV (power lines) conforming to EN/IEC 61000-4-4