All categories
Compare Cart

TM5SAI2PH - Analog input module, Modicon TM5, 2I, temperature probe PT100/PT1000, 16 bits - Schneider Electric

Expected in 2-4 weeks
TM5SAI2PH - Analog input module, Modicon TM5, 2I, temperature probe PT100/PT1000, 16 bits - Schneider Electric - Analog input module, Modicon TM5, 2I, temperature probe PT100/PT1000, 16 bits - Schneider Electric - 0
TM5SAI2PH - Analog input module, Modicon TM5, 2I, temperature probe PT100/PT1000, 16 bits - Schneider Electric
374,99 € excl. VAT
457,48 € incl. VAT
Text About:
Analog input module, Modicon TM5, 2I, temperature probe PT100/PT1000, 16 bits - Schneider Electric
457,48 €
SPECIFICATIONS
Main
Analogue input resolution 16 bits
Complementary
product compatibility Logic controller
Motion controller
range compatibility Modicon M258
Modicon LMC058
Product certifications cULus
CSA
GOST-R
C-Tick
Product or component type Analog input module
[us] rated supply voltage 24 V DC -15...20 %
Current consumption 2 mA at 5 V DC bus
46 mA at 24 V DC input/output
marking CE
temperature coefficient 0.004 %FS/°C, analogue input type: temperature probe
Analogue input number 2
Common mode rejection > 95 dB
maximum power dissipation in w 1.11 W
Analogue input type Pt 100/Pt 1000 temperature probe - 200...850 °C
isolation 500 Vrms AC insulation between channel and bus
No insulation between channels
Colour White
Local signalling 1 LED green for power supply
1 LED red for power supply
2 LEDs green for input status
Disturbance radiated/conducted CISPR 11
Net weight 0.025 kg
measurement error < 0.037 % of full scale - 200...850 °C Pt 100/Pt 1000 at 25 °C
Measurement resolution 0.1 °C
Pollution degree 2 conforming to IEC 60664
Non-linearity 0.00015 %FS, analogue input type: temperature probe
Resistance to electrostatic discharge 4 kV on contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to EN/IEC 61000-4-2
Shock resistance 15 gn for 11 ms
Resistance to electromagnetic fields 1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
Surge withstand 0.5 kV differential mode conforming to EN/IEC 61000-4-5
1 kV common mode conforming to EN/IEC 61000-4-5
Supply Internal
Type of cable Shielded cable
Environment
Ambient air temp for storage/transportation -25…70 °C
ip degree of protection IP20 conforming to IEC 61131-2
operating altitude 0...2000 m
Range of product Modicon TM5
ambient air temperature for operation 0…55 °C without derating (horizontal installation)
0…60 °C with derating factor (horizontal installation)
0…50 °C (vertical installation)
electromagnetic compatibility EN/IEC 61000-4-6
standards UL 508
CSA C22.2 No 142
IEC 61131-2
CSA C22.2 No 213
Storage altitude 0…3000 m
relative humidity 5…95 % without condensation
vibration resistance 1 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on DIN rail
resistance to fast transients 1 kV (I/O) conforming to EN/IEC 61000-4-4
1 kV (shielded cable) conforming to EN/IEC 61000-4-4
2 kV (power lines) conforming to EN/IEC 61000-4-4
Recently viewed
374,99 € excl. VAT
457,48 € incl. VAT
Expected in 2-4 weeks