Complementary
product compatibility
Modicon M241 logic controller
Modicon M251 logic controller
range compatibility
Modicon M251
Modicon M241
Product certifications
C-Tick
cULus
Handle front plate colour
90 mm
Product or component type
Profibus DP communication module
Current consumption
290 mA at 5 V DC for communication bus
marking
CE
width (w)
25 mm
Local signalling
1 LED (green/yellow) for power supply
1 LED (green/red) for communication
Net weight
0.1 kg
communication port protocol
Profibus DP V0
Profibus DP V1
Integrated connection type
Profibus DP: female SUB-D 9 connector
Mounting support
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
depth
90 mm
power dissipation in w
1.5 W
Pollution degree
2
electrical connection
Screw connector terminal for connecting the functional ground
SUB-D 9 1 female connector for connecting Profibus
Insulation
Between bus and internal logic at 1000 V DC
Resistance to electrostatic discharge
8 kV in air conforming to EN/IEC 61000-4-2
4 kV on contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to Marine specification (LR, ABS, DNV, GL)
6 kV on contact conforming to Marine specification (LR, ABS, DNV, GL)
Shock resistance
15 gn for 11 ms
Resistance to electromagnetic fields
10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
Surge withstand
1 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5
2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5
2 kV relay output common mode conforming to EN/IEC 61000-4-5
1 kV I/O common mode conforming to EN/IEC 61000-4-5
1 kV shielded cable common mode conforming to EN/IEC 61000-4-5
0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5
1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5
1 kV relay output differential mode conforming to EN/IEC 61000-4-5
0.5 kV I/O differential mode conforming to EN/IEC 61000-4-5
Transmission rate
1.5 Mbit/s for bus length of 200 m
500 kbit/s for bus length of 400 m
187.5 kbit/s for bus length of 1000 m
9.6...93.75 kbit/s for bus length of 1200 m
3...12 Mbit/s for bus length of 100 m
Environment
Ambient air temp for storage/transportation
-25…70 °C
ip degree of protection
IP20 with protective cover in place
operating altitude
0...2000 m
ambient air temperature for operation
-10…55 °C horizontal installation
-10…50 °C vertical installation
Resistance to conducted disturbances
10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
standards
EN/IEC 61131-2
UL 508
EIA-485
Storage altitude
0…3000 m
relative humidity
10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
electromagnetic emission
Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011
Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 40 dBμV/m QP class A at 30…230 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 60...54 dBμV/m QP at 30…100 MHz conforming to Marine specification (LR, ABS, DNV, GL)
Radiated emissions - test level: 24 dBμV/m QP at 156…165 MHz conforming to Marine specification (LR, ABS, DNV, GL)
Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A at 230…1000 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 80...50 dμV/m QP at 150…30000 kHz conforming to Marine specification (LR, ABS, DNV, GL)
Radiated emissions - test level: 54 dBμV/m QP at 100…2000 MHz conforming to Marine specification (LR, ABS, DNV, GL)
vibration resistance
1 mm at 5…13.2 Hz on symmetrical rail
3 gn at 8.7…150 Hz on symmetrical rail
1 mm at 5…13.2 Hz on panel mounting
0.7 gn at 13.2…100 Hz on panel mounting
resistance to fast transients
2 kV (power lines) conforming to EN/IEC 61000-4-4
2 kV (relay output) conforming to EN/IEC 61000-4-4
1.5 kV (I/O) conforming to EN/IEC 61000-4-4
1 kV (Ethernet line) conforming to EN/IEC 61000-4-4