Complementary
[ics] rated service breaking capacity
4 A 24 V 50 ms DC-13 relay output
[ith] conventional thermal current
18 A
Product certifications
ANSI Haz Loc Class 1 Division 2 (pending)
UL 61010-2-201
EAC
TÜV
RCM
CSA Haz Loc Class 1 Division 2 (pending)
CSA 61010-2-201 (pending)
Handle front plate colour
94 mm
Product or component type
Safety module
[uimp] rated impulse withstand voltage
4 kV overvoltage category III conforming to IEC 60647-5-1
[us] rated supply voltage
24 V - 15...20 % DC
Current consumption
100 mA at 24 V DC external supply
Connections - terminals
Captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34
Captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34
Captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34
Captive spring terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34
Captive spring terminals, removable terminal block 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel 13-14, 23-24, 33-34
Captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² flexible without cable end other terminals
Captive spring terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² solid without cable end other terminals
Captive spring terminals, removable terminal block 1 x 0.25...1 x 0.5 mm² flexible with cable end, with bezel other terminals
Captive spring terminals, removable terminal block 1 x 0.25...1 x 1.5 mm² flexible with cable end, without bezel other terminals
Associated fuse rating
4 A gG or gL for relay output conforming to EN/IEC 60947-5-1
6 A fast blow for relay output conforming to EN/IEC 60947-5-1
marking
EFUP 10
CE
UL
EAC
RCM
CSA
TÜV
minimum output current
10 mA for relay output
output thermal current
6 A per relay for relay output
Output type
Relay instantaneous opening, 3 NO circuit(s), potential free
Function of module
Emergency stop monitoring 1-channel wiring
Emergency stop monitoring 2-channel wiring
Monitoring of a movable guard with 2 switches and automatic start
safety reliability data
DC = 95 % conforming to EN/ISO 13849-1
PFHd = 5E-9 1/h conforming to IEC 61508-1 1 operation/hour DC-13 24 V DC, <4 A
PFHd = 30E-9 1/h conforming to IEC 61508-1 60 operations/hour DC-13 24 V DC, <1 A
MTTFd = 500 years conforming to EN/ISO 13849-1 1 operation/hour DC-13 24 V DC, <4 A
MTTFd = 85 years conforming to EN/ISO 13849-1 60 operations/hour DC-13 24 V DC, <1 A
SFF = 95 % conforming to IEC 61508-1
HFT = 1 conforming to IEC 61508-1
Type = A conforming to IEC 61508-1
output voltage
10 V relay output
width (w)
43.7 mm
mechanical robustness
Bumps 6 ms 300 shocks (25 gn) conforming to IEC 60068-2-27
Local signalling
8 LEDs (green/red) for user
Net weight
0.19 kg
Maximum cable distance between devices
30 m
Maximum response time on input open
40 ms
Mounting support
Top hat type TH35-7.5 rail conforming to IEC 60715
Top hat type TH35-15 rail conforming to IEC 60715
wall mount using attached fasteners
depth
73 mm
Pollution degree
2
Power consumption in w
0.2 W at 5 V DC
3.6 W at 24 V DC
electrical connection
Spring terminal
Maximum switching voltage
230 V utilisation category AC-15 at 50 Hz (relay instantaneous opening)
24 V utilisation category DC-13 (relay instantaneous opening)
Number of safety circuits
3 NO for relay instantaneous opening
input protection type
Internal, electronic
Synchronisation time between inputs
Unlimited
Resistance to electrostatic discharge
8 kV in air conforming to EN/IEC 61000-4-2
6 kV on contact conforming to EN/IEC 61000-4-2
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Safety level
Can reach PL e/category 4 conforming to EN/ISO 13849-1: 2008
Can reach PL e/category 4 conforming to EN/ISO 13849-2: 2012
Can reach SILCL 3 conforming to EN/IEC 62061: 2005
Can reach SIL 3 conforming to EN/IEC 61508: 2010
Resistance to electromagnetic fields
10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
Surge withstand
1 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5 DC
1 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5 DC
Environment
Ambient air temp for storage/transportation
-25…70 °C
ip degree of protection
IP20 (terminals) conforming to EN/IEC 60529
operating altitude
0...2000 m
Range of product
Modicon TM3 Safety
ambient air temperature for operation
-10…55 °C horizontal installation
electromagnetic compatibility
Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2
Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz to 1 GHz) conforming to EN/IEC 61000-4-3
Susceptibility to electromagnetic fields - test level: 3 V/m (1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3
Susceptibility to electromagnetic fields - test level: 1 V/m (2 GHz...3 GHz) conforming to EN/IEC 61000-4-3
Magnetic field at power frequency - test level: 30 A/m (50...60 Hz) conforming to EN/IEC 61000-4-8
Electrical fast transient/burst immunity test - test level: 3 kV (power lines (DC)) conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test - test level: 2 kV (I/O) conforming to EN/IEC 61000-4-4
1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to EN/IEC 61000-4-5
Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6
Radiated emission - test level: 40 dBµV/m class A (24 V) conforming to EN 55011
Radiated emission - test level: 47 dBµV/m class A (24 V) conforming to EN 55011
Resistance to conducted disturbances
10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
standards
EN/ISO 13850
EN/IEC 60947-5-1
EN 1088/ISO 14119
EN 60204-1
EN/IEC 60947-1
Storage altitude
0…3000 m
relative humidity
10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
electromagnetic emission
Radiated emissions - test level: 50 dBµV/m class A ( 24 V DC) at 30…230 Hz conforming to IEC 61131-3
Radiated emissions - test level: 57 dBµV/m class A ( 24 V DC) at 230…1000 Hz conforming to IEC 61131-3
vibration resistance
+/- 3.5 mm (f= 5…150 Hz) conforming to IEC 60068-2-6
resistance to fast transients
3 kV for power lines (DC) (DC) conforming to EN/IEC 61000-4-4
2 kV for I/O lines conforming to EN/IEC 61000-4-4
resistance to magnetic fields
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8