Main
battery type
BR2032 lithium non-rechargeable, battery life: 4 year(s)
Complementary
Application structure
4 cyclic master tasks
8 event tasks
3 cyclic master tasks + 1 freewheeling task
8 external event tasks
data storage equipment
<= 16 GB SD card (optional)
memory capacity
8 MB for program
64 MB for system memory RAM
Product certifications
cULus
CSA
Handle front plate colour
90 mm
Product or component type
Logic controller
[us] rated supply voltage
24 V DC
inrush current
50 A
marking
CE
Data backed up
128 MB built-in flash memory for backup of user programs
clock drift
<= 60 s/month at 25 °C
maximum number of connections
8 Modbus server
8 Modbus client
16 Ethernet/IP target
4 FTP server
10 web server
8 SoMachine protocol
width (w)
54 mm
supply voltage limits
20.4…28.8 V
Local signalling
1 LED (green) for PWR
1 LED (green) for RUN
1 LED (red) for module error (ERR)
1 LED (red) for I/O error (I/O)
1 LED (green) for SD card access (SD)
1 LED (red) for BAT
1 LED (green) for SL
1 LED (red) for bus fault on TM4 (TM4)
1 LED (green) for Ethernet activity (ETH1)
1 LED (green) for Ethernet activity (ETH2)
Net weight
0.22 kg
Realtime clock
With
Number of slave
16 EtherNet/IP:
64 Modbus TCP:
Communication service
Downloading
IEC VAR ACCESS
Modbus TCP client
Modbus TCP server
Modbus TCP slave device
Monitoring
NGVL
Programming
Updating firmware
SMS notifications
DHCP client (Eth1)
DHCP server (Eth2)
Ethernet/IP originator (Eth2)
Ethernet/IP target (Eth1, Eth2)
Ethernet/IP scanner (Eth2)
Modbus TCP I/O Scanner and Messaging (Eth2)
FDR
FTP client/server
SNMP client/server
SQL client
Send and receive email from the controller based on TCP/UDP library
Web server (WebVisu & XWeb system)
OPC UA server
DNS client
communication port protocol
USB port: USB - SoMachine-Network
Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network
Immunity to microbreaks
10 ms
Integrated connection type
USB port with mini B USB 2.0 connector
Non isolated serial link serial with RJ45 connector and RS232/RS485 interface
Dual-port Ethernet 1 with RJ45 connector
Ethernet port Ethernet 2 with RJ45 connector
Mounting support
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
depth
95 mm
backup time
2 years at 25 °C
Pollution degree
2
Power consumption in w
32.6…40.4 W (with max number of I/O expansion module)
electrical connection
removable screw terminal blockpower supply (pitch 5.08 mm)
Maximum number of i/o expansion module
7 (local I/O-Architecture)
14 (remote I/O-Architecture)
port ethernet
Ethernet 1 marking 10BASE-T/100BASE-TX - 2 copper cable
Ethernet 2 marking 10BASE-T/100BASE-TX - 1 copper cable
Insulation
Non-insulated between supply and internal logic
Between supply and ground at 500 V AC
Execution time for 1 kinstruction
0.3 ms for event and periodic task
0.7 ms for other instruction
Resistance to electrostatic discharge
8 kV in air conforming to EN/IEC 61000-4-2
4 kV on contact conforming to EN/IEC 61000-4-2
Shock resistance
15 gn for 11 ms
cycle time
10 ms 16 EtherNet/IP
64 ms 64 Modbus TCP
Resistance to electromagnetic fields
10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
Surge withstand
1 kV shielded cable common mode conforming to EN/IEC 61000-4-5
1 kV power lines common mode conforming to EN/IEC 61000-4-5
0.5 kV power lines differential mode conforming to EN/IEC 61000-4-5
Supply
(serial)serial link supply: 5 V, <200 mA
Web services
Web server
Transmission rate
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
480 Mbit/s for bus length of 3 m for USB
Environment
Ambient air temp for storage/transportation
-25…70 °C
ip degree of protection
IP20 with protective cover in place
operating altitude
0...2000 m
Range of product
Modicon M251
ambient air temperature for operation
-10…35 °C (vertical installation)
-10…55 °C (horizontal installation)
Resistance to conducted disturbances
10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
standards
ANSI/ISA 12-12-01
CSA C22.2 No 142
CSA C22.2 No 213
EN/IEC 61131-2:2007
Marine specification (LR, ABS, DNV, GL)
UL 1604
UL 508
Storage altitude
0…3000 m
relative humidity
10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
electromagnetic emission
Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011
Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/IEC 55011
vibration resistance
3.5 mm at 5…8.4 Hz on symmetrical rail
3 gn at 8.4…150 Hz on symmetrical rail
3.5 mm at 5…8.4 Hz on panel mounting
3 gn at 8.4…150 Hz on panel mounting
resistance to fast transients
2 kV (power lines) conforming to EN/IEC 61000-4-4
1 kV (Ethernet line) conforming to EN/IEC 61000-4-4
1 kV (serial link) conforming to EN/IEC 61000-4-4