Complementary
Absolute accuracy error
+/- 1 % of full scale for analog input
data storage equipment
2 GB SD card (optional)
maximum power consumption in va
58 VA at 100...240 V with max number of I/O expansion module
35 VA at 100...240 V without I/O expansion module
memory capacity
256 kB for user application and data RAM with 10000 instructions
256 kB for internal variables RAM
Product certifications
LR
cULus
IACS E10
CSA
ABS
DNV-GL
EAC
RCM
response time
35 µs turn-off, I2...I5 terminal(s) for input
10 ms turn-on for output
10 ms turn-off for output
5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input
35 µs turn-on, other terminals terminal(s) for input
5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input
100 µs turn-off, other terminals terminal(s) for input
Handle front plate colour
90 mm
Product or component type
Logic controller
[us] rated supply voltage
100...240 V AC
inrush current
40 A
marking
CE
reset time
1 s
Analogue input number
2 at 0...10 V
Configurable filtering time
0 ms for input
3 ms for input
12 ms for input
Data backed up
256 kB built-in flash memory for backup of application and data
Discrete i/o number
24
Discrete output current
2 A
clock drift
<= 30 s/month at 25 °C
Discrete input logic
Sink or source (positive/negative)
width (w)
110 mm
Counter function
A/B
Single phase
Pulse/direction
Maximum current per output common
4 A at COM 2
7 A at COM 0
7 A at COM 1
network frequency
50/60 Hz
supply voltage limits
85…264 V
switching frequency
20 switching operations/minute with maximum load
Counting input number
4 fast input (HSC mode) at 100 kHz 32 bits
Discrete input voltage
24 V
Local signalling
1 LED (green) for PWR
1 LED (green) for RUN
1 LED (red) for module error (ERR)
1 LED (green) for SD card access (SD)
1 LED (red) for BAT
1 LED per channel (green) for I/O state
1 LED (green) for SL
Ethernet network activity (green) for ACT
Ethernet network link (yellow) for Link (Link Status)
Discrete input number
14, discrete input conforming to IEC 61131-2 Type 1
Net weight
0.395 kg
Realtime clock
With
Discrete output type
Relay normally open
Maximum cable distance between devices
Shielded cable: <10 m for fast input
Unshielded cable: <30 m for output
Unshielded cable: <30 m for digital input
Unshielded cable: <1 m for analog input
Communication service
Modbus TCP server
Modbus TCP slave device
DHCP client
Modbus TCP client
Ethernet/IP adapter
Discrete output voltage
5...125 V DC
5...250 V AC
Maximum size of object areas
255 %TM timers
512 %M memory bits
8000 %MW memory words
255 %C counters
512 %KW constant words
voltage state 1 guaranteed
>= 15 V for input
communication port protocol
USB port: USB - SoMachine-Network
Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network
Ethernet
Discrete output number
10 relay
Immunity to microbreaks
10 ms
input impedance
3.4 kOhm for discrete input
100 kOhm for analog input
4.9 kOhm for fast input
Integrated connection type
USB port with mini B USB 2.0 connector
Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface
Ethernet with RJ45 connector
Mounting support
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
depth
70 mm
mechanical durability
20000000 cycles for relay output
backup time
1 year at 25 °C (by interruption of power supply)
electrical durability
100000 cycles AC-12, 120 V, 240 VA, resistive
100000 cycles AC-12, 240 V, 480 VA, resistive
300000 cycles AC-12, 120 V, 80 VA, resistive
300000 cycles AC-12, 240 V, 160 VA, resistive
100000 cycles AC-15, cos phi = 0.35, 120 V, 60 VA, inductive
100000 cycles AC-15, cos phi = 0.35, 240 V, 120 VA, inductive
300000 cycles AC-15, cos phi = 0.35, 120 V, 18 VA, inductive
300000 cycles AC-15, cos phi = 0.35, 240 V, 36 VA, inductive
100000 cycles AC-14, cos phi = 0.7, 120 V, 120 VA, inductive
100000 cycles AC-14, cos phi = 0.7, 240 V, 240 VA, inductive
300000 cycles AC-14, cos phi = 0.7, 120 V, 36 VA, inductive
300000 cycles AC-14, cos phi = 0.7, 240 V, 72 VA, inductive
100000 cycles DC-12, 24 V, 48 W, resistive
300000 cycles DC-12, 24 V, 16 W, resistive
100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms)
300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms)
output voltage limits
125 V DC
277 V AC
voltage state 0 guaranteed
<= 5 V for input
Pollution degree
<= 2
electrical connection
removable screw terminal block for inputs
removable screw terminal block for outputs
terminal block, 3 terminal(s) for connecting the 24 V DC power supply
connector, 4 terminal(s) for analogue inputs
Mini B USB 2.0 connector for a programming terminal
execution time per instruction
0.2 µs Boolean
Permitted overload on inputs
+/- 30 V DC for 5 min (maximum) for analog input
+/- 13 V DC (permanent) for analog input
Maximum number of i/o expansion module
7 for transistor output
7 for relay output
port ethernet
10BASE-T/100BASE-TX 1 port with 100 m copper cable
Insulation
Between input and internal logic at 500 V AC
Non-insulated between analogue input and internal logic
Non-insulated between analogue inputs
Between supply and ground at 1500 V AC
Between sensor power supply and ground at 500 V AC
Between input and ground at 500 V AC
Between output and ground at 1500 V AC
Between supply and internal logic at 2300 V AC
Between sensor power supply and internal logic at 500 V AC
Between output and internal logic at 2300 V AC
Between Ethernet terminal and internal logic at 500 V AC
Between supply and sensor power supply at 2300 V AC
Exct time for event task
60 µs response time
Sensor power supply
24 V DC at 250 mA supplied by the controller
Execution time for 1 kinstruction
0.3 ms for event and periodic task
Lsb value
10 mV
Resistance to electrostatic discharge
8 kV in air conforming to EN/IEC 61000-4-2
4 kV on contact conforming to EN/IEC 61000-4-2
Shock resistance
98 m/s² for 11 ms
conversion time
1 ms per channel + 1 controller cycle time for analogue input analog input
Resistance to electromagnetic fields
10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
Surge withstand
2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5
2 kV relay output common mode conforming to EN/IEC 61000-4-5
1 kV I/O common mode conforming to EN/IEC 61000-4-5
1 kV shielded cable common mode conforming to EN/IEC 61000-4-5
0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5
1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5
1 kV relay output differential mode conforming to EN/IEC 61000-4-5
0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5
Supply
(serial)serial link supply: 5 V, <200 mA
Protection type
Without protection at 5 A
Transmission rate
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
480 Mbit/s for USB
Environment
Ambient air temp for storage/transportation
-25…70 °C
ip degree of protection
IP20 with protective cover in place
operating altitude
0...2000 m
Range of product
Modicon M221
ambient air temperature for operation
-10…55 °C (horizontal installation)
-10…35 °C (vertical installation)
Environmental characteristics
Ordinary and hazardous location
Resistance to conducted disturbances
10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
standards
EN/IEC 61010-2-201
EN/IEC 61131-2
EN/IEC 60664-1
Storage altitude
0…3000 m
relative humidity
10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
electromagnetic emission
Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011
Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to EN/IEC 55011
Regulation loop
Adjustable PID regulator up to 14 simultaneous loops
vibration resistance
3.5 mm at 5…8.4 Hz on symmetrical rail
3.5 mm at 5…8.4 Hz on panel mounting
1 gn at 8.4…150 Hz on symmetrical rail
1 gn at 8.4…150 Hz on panel mounting
resistance to fast transients
2 kV (power lines) conforming to EN/IEC 61000-4-4
2 kV (relay output) conforming to EN/IEC 61000-4-4
1 kV (I/O) conforming to EN/IEC 61000-4-4
1 kV (Ethernet line) conforming to EN/IEC 61000-4-4
1 kV (serial link) conforming to EN/IEC 61000-4-4
resistance to magnetic fields
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8