SPECIFICATIONS
Main
Analogue input resolution 10 bits
Discrete input voltage type DC
Power supply output current 0.52 A 5 V for expansion bus
0.16 A 24 V for expansion bus
Discrete input current 7 mA for discrete input
5 mA for fast input
Minimum load 1 mA at 5 V DC for relay output
battery type BR2032 lithium non-rechargeable, battery life: 4 year(s)
Complementary
Absolute accuracy error +/- 1 % of full scale for analog input
data storage equipment 2 GB SD card (optional)
maximum power consumption in va 55 VA at 100...240 V with max number of I/O expansion module
32 VA at 100...240 V without I/O expansion module
memory capacity 256 kB for user application and data RAM with 10000 instructions
256 kB for internal variables RAM
Product certifications CSA
LR
ABS
IACS E10
DNV-GL
RCM
cULus
EAC
response time 35 µs turn-off, I2...I5 terminal(s) for input
10 ms turn-on for output
10 ms turn-off for output
5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input
35 µs turn-on, other terminals terminal(s) for input
5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input
100 µs turn-off, other terminals terminal(s) for input
Handle front plate colour 90 mm
Product or component type Logic controller
[us] rated supply voltage 100...240 V AC
inrush current 40 A
marking CE
reset time 1 s
Analogue input number 2 at 0...10 V
Configurable filtering time 0 ms for input
3 ms for input
12 ms for input
Data backed up 256 kB built-in flash memory for backup of application and data
Discrete i/o number 24
Discrete output current 2 A
clock drift <= 30 s/month at 25 °C
Discrete input logic Sink or source (positive/negative)
width (w) 110 mm
Counter function A/B
Single phase
Pulse/direction
Maximum current per output common 4 A at COM 2
7 A at COM 0
7 A at COM 1
network frequency 50/60 Hz
supply voltage limits 85…264 V
switching frequency 20 switching operations/minute with maximum load
Counting input number 4 fast input (HSC mode) at 100 kHz 32 bits
Discrete input voltage 24 V
Local signalling 1 LED (green) for PWR
1 LED (green) for RUN
1 LED (red) for module error (ERR)
1 LED (green) for SD card access (SD)
1 LED (red) for BAT
1 LED (green) for SL1
1 LED (green) for SL2
1 LED per channel (green) for I/O state
Discrete input number 14, discrete input conforming to IEC 61131-2 Type 1
Net weight 0.395 kg
Realtime clock With
Discrete output type Relay normally open
Maximum cable distance between devices Shielded cable: <10 m for fast input
Unshielded cable: <30 m for output
Unshielded cable: <30 m for digital input
Unshielded cable: <1 m for analog input
Discrete output voltage 5...125 V DC
5...250 V AC
Maximum size of object areas 255 %C counters
8000 %MW memory words
512 %M memory bits
512 %KW constant words
255 %TM timers
voltage state 1 guaranteed >= 15 V for input
communication port protocol USB port: USB - SoMachine-Network
Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network
Discrete output number 10 relay
Immunity to microbreaks 10 ms
input impedance 3.4 kOhm for discrete input
100 kOhm for analog input
4.9 kOhm for fast input
Integrated connection type USB port with mini B USB 2.0 connector
Non isolated serial link serial 1 with RJ45 connector and RS485 interface
Non isolated serial link serial 2 with RJ45 connector and RS232/RS485 interface
Mounting support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
depth 70 mm
mechanical durability 20000000 cycles for relay output
backup time 1 year at 25 °C (by interruption of power supply)
electrical durability 100000 cycles AC-12, 120 V, 240 VA, resistive
100000 cycles AC-12, 240 V, 480 VA, resistive
300000 cycles AC-12, 120 V, 80 VA, resistive
300000 cycles AC-12, 240 V, 160 VA, resistive
100000 cycles AC-15, cos phi = 0.35, 120 V, 60 VA, inductive
100000 cycles AC-15, cos phi = 0.35, 240 V, 120 VA, inductive
300000 cycles AC-15, cos phi = 0.35, 120 V, 18 VA, inductive
300000 cycles AC-15, cos phi = 0.35, 240 V, 36 VA, inductive
100000 cycles AC-14, cos phi = 0.7, 120 V, 120 VA, inductive
100000 cycles AC-14, cos phi = 0.7, 240 V, 240 VA, inductive
300000 cycles AC-14, cos phi = 0.7, 120 V, 36 VA, inductive
300000 cycles AC-14, cos phi = 0.7, 240 V, 72 VA, inductive
100000 cycles DC-12, 24 V, 48 W, resistive
300000 cycles DC-12, 24 V, 16 W, resistive
100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms)
300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms)
output voltage limits 125 V DC
277 V AC
voltage state 0 guaranteed <= 5 V for input
Pollution degree <= 2
electrical connection removable screw terminal block for inputs
removable screw terminal block for outputs
terminal block, 3 terminal(s) for connecting the 24 V DC power supply
connector, 4 terminal(s) for analogue inputs
Mini B USB 2.0 connector for a programming terminal
execution time per instruction 0.2 µs Boolean
Permitted overload on inputs +/- 30 V DC for 5 min (maximum) for analog input
+/- 13 V DC (permanent) for analog input
Maximum number of i/o expansion module 7 for transistor output
7 for relay output
Insulation Between input and internal logic at 500 V AC
Non-insulated between analogue input and internal logic
Non-insulated between analogue inputs
Between supply and ground at 1500 V AC
Between sensor power supply and ground at 500 V AC
Between input and ground at 500 V AC
Between output and ground at 1500 V AC
Between supply and internal logic at 2300 V AC
Between sensor power supply and internal logic at 500 V AC
Between output and internal logic at 2300 V AC
Between Ethernet terminal and internal logic at 500 V AC
Between supply and sensor power supply at 2300 V AC
Exct time for event task 60 µs response time
Sensor power supply 24 V DC at 250 mA supplied by the controller
Execution time for 1 kinstruction 0.3 ms for event and periodic task
Lsb value 10 mV
Resistance to electrostatic discharge 8 kV in air conforming to EN/IEC 61000-4-2
4 kV on contact conforming to EN/IEC 61000-4-2
Shock resistance 98 m/s² for 11 ms
conversion time 1 ms per channel + 1 controller cycle time for analogue input analog input
Resistance to electromagnetic fields 10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
Surge withstand 2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5
2 kV relay output common mode conforming to EN/IEC 61000-4-5
1 kV I/O common mode conforming to EN/IEC 61000-4-5
1 kV shielded cable common mode conforming to EN/IEC 61000-4-5
0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5
1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5
1 kV relay output differential mode conforming to EN/IEC 61000-4-5
0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5
Supply (serial)serial link supply: 5 V, <200 mA
Protection type Without protection at 5 A
Transmission rate 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
480 Mbit/s for USB
Environment
Ambient air temp for storage/transportation -25…70 °C
ip degree of protection IP20 with protective cover in place
operating altitude 0...2000 m
Range of product Modicon M221
ambient air temperature for operation -10…55 °C (horizontal installation)
-10…35 °C (vertical installation)
Environmental characteristics Ordinary and hazardous location
Resistance to conducted disturbances 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
standards EN/IEC 61010-2-201
EN/IEC 60664-1
EN/IEC 61131-2
Storage altitude 0…3000 m
relative humidity 10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
electromagnetic emission Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011
Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to EN/IEC 55011
Regulation loop Adjustable PID regulator up to 14 simultaneous loops
vibration resistance 3.5 mm at 5…8.4 Hz on symmetrical rail
3.5 mm at 5…8.4 Hz on panel mounting
1 gn at 8.4…150 Hz on symmetrical rail
1 gn at 8.4…150 Hz on panel mounting
resistance to fast transients 2 kV (power lines) conforming to EN/IEC 61000-4-4
2 kV (relay output) conforming to EN/IEC 61000-4-4
1 kV (I/O) conforming to EN/IEC 61000-4-4
1 kV (Ethernet line) conforming to EN/IEC 61000-4-4
1 kV (serial link) conforming to EN/IEC 61000-4-4
resistance to magnetic fields 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8