All categories
Compare Cart

TM221C16R - Modicon M221, Logic controller, 16 inputs/outputs, 7 relay outputs, 100?¦240 V AC - Schneider Electric

Expected in 2-4 weeks
TM221C16R - Modicon M221, Logic controller, 16 inputs/outputs, 7 relay outputs, 100?¦240 V AC - Schneider Electric - Modicon M221, Logic controller, 16 inputs/outputs, 7 relay outputs, 100?¦240 V AC - Schneider Electric - 0
TM221C16R - Modicon M221, Logic controller, 16 inputs/outputs, 7 relay outputs, 100?¦240 V AC - Schneider Electric
230,23 € excl. VAT
280,88 € incl. VAT
Text About:
Modicon M221, Logic controller, 16 inputs/outputs, 7 relay outputs, 100?¦240 V AC - Schneider Electric
280,88 €
SPECIFICATIONS
Main
Analogue input resolution 10 bits
Discrete input voltage type DC
Power supply output current 0.325 A 5 V for expansion bus
0.12 A 24 V for expansion bus
Discrete input current 7 mA for discrete input
5 mA for fast input
Minimum load 1 mA at 5 V DC for relay output
battery type BR2032 lithium non-rechargeable, battery life: 4 year(s)
Complementary
Absolute accuracy error +/- 1 % of full scale for analog input
data storage equipment 2 GB SD card (optional)
maximum power consumption in va 46 VA at 100...240 V with max number of I/O expansion module
31 VA at 100...240 V without I/O expansion module
memory capacity 256 kB for user application and data RAM with 10000 instructions
256 kB for internal variables RAM
Product certifications IACS E10
RCM
CSA
ABS
LR
DNV-GL
EAC
cULus
response time 35 µs turn-off, I2...I5 terminal(s) for input
10 ms turn-on for output
10 ms turn-off for output
5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input
35 µs turn-on, other terminals terminal(s) for input
5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input
100 µs turn-off, other terminals terminal(s) for input
Handle front plate colour 90 mm
Product or component type Logic controller
[us] rated supply voltage 100...240 V AC
inrush current 40 A
marking CE
reset time 1 s
Analogue input number 2 at 0...10 V
Configurable filtering time 0 ms for input
3 ms for input
12 ms for input
Data backed up 256 kB built-in flash memory for backup of application and data
Discrete i/o number 16
Discrete output current 2 A
clock drift <= 30 s/month at 25 °C
Discrete input logic Sink or source (positive/negative)
width (w) 95 mm
Counter function Single phase
Frequency meter
Dual phase (quadrature)
Dual phase (pulse/direction)
Maximum current per output common 6 A at COM 1
7 A at COM 0
network frequency 50/60 Hz
supply voltage limits 85…264 V
switching frequency 20 switching operations/minute with maximum load
Counting input number 4 fast input (HSC mode) at 100 kHz 32 bits
Discrete input voltage 24 V
Local signalling 1 LED (green) for PWR
1 LED (green) for RUN
1 LED (red) for module error (ERR)
1 LED (green) for SD card access (SD)
1 LED (red) for BAT
1 LED (green) for SL1
1 LED (green) for SL2
1 LED per channel (green) for I/O state
Discrete input number 9, discrete input conforming to IEC 61131-2 Type 1
Net weight 0.346 kg
Realtime clock With
Discrete output type Relay normally open
Maximum cable distance between devices Shielded cable: <10 m for fast input
Unshielded cable: <30 m for output
Unshielded cable: <30 m for digital input
Unshielded cable: <1 m for analog input
Discrete output voltage 5...125 V DC
5...250 V AC
Maximum size of object areas 512 %KW constant words
512 %M memory bits
255 %C counters
8000 %MW memory words
255 %TM timers
voltage state 1 guaranteed >= 15 V for input
communication port protocol USB port: USB - SoMachine-Network
Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network
Discrete output number 7 relay
Immunity to microbreaks 10 ms
input impedance 3.4 kOhm for discrete input
100 kOhm for analog input
4.9 kOhm for fast input
Integrated connection type USB port with mini B USB 2.0 connector
Non isolated serial link serial 1 with RJ45 connector and RS485 interface
Non isolated serial link serial 2 with RJ45 connector and RS232/RS485 interface
Mounting support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
depth 70 mm
mechanical durability 20000000 cycles for relay output
backup time 1 year at 25 °C (by interruption of power supply)
electrical durability 100000 cycles AC-12, 120 V, 240 VA, resistive
100000 cycles AC-12, 240 V, 480 VA, resistive
300000 cycles AC-12, 120 V, 80 VA, resistive
300000 cycles AC-12, 240 V, 160 VA, resistive
100000 cycles AC-15, cos phi = 0.35, 120 V, 60 VA, inductive
100000 cycles AC-15, cos phi = 0.35, 240 V, 120 VA, inductive
300000 cycles AC-15, cos phi = 0.35, 120 V, 18 VA, inductive
300000 cycles AC-15, cos phi = 0.35, 240 V, 36 VA, inductive
100000 cycles AC-14, cos phi = 0.7, 120 V, 120 VA, inductive
100000 cycles AC-14, cos phi = 0.7, 240 V, 240 VA, inductive
300000 cycles AC-14, cos phi = 0.7, 120 V, 36 VA, inductive
300000 cycles AC-14, cos phi = 0.7, 240 V, 72 VA, inductive
100000 cycles DC-12, 24 V, 48 W, resistive
300000 cycles DC-12, 24 V, 16 W, resistive
100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms)
300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms)
output voltage limits 125 V DC
277 V AC
voltage state 0 guaranteed <= 5 V for input
Pollution degree <= 2
electrical connection removable screw terminal block for inputs
removable screw terminal block for outputs
terminal block, 3 terminal(s) for connecting the 24 V DC power supply
connector, 4 terminal(s) for analogue inputs
Mini B USB 2.0 connector for a programming terminal
execution time per instruction 0.2 µs Boolean
Permitted overload on inputs +/- 30 V DC for 5 min (maximum) for analog input
+/- 13 V DC (permanent) for analog input
Maximum number of i/o expansion module 4 for transistor output
4 for relay output
Insulation Between input and internal logic at 500 V AC
Non-insulated between analogue input and internal logic
Non-insulated between analogue inputs
Between supply and ground at 1500 V AC
Between sensor power supply and ground at 500 V AC
Between input and ground at 500 V AC
Between output and ground at 1500 V AC
Between supply and internal logic at 2300 V AC
Between sensor power supply and internal logic at 500 V AC
Between output and internal logic at 2300 V AC
Between Ethernet terminal and internal logic at 500 V AC
Between supply and sensor power supply at 2300 V AC
Exct time for event task 60 µs response time
Sensor power supply 24 V DC at 250 mA supplied by the controller
Execution time for 1 kinstruction 0.3 ms for event and periodic task
Lsb value 10 mV
Resistance to electrostatic discharge 8 kV in air conforming to EN/IEC 61000-4-2
4 kV on contact conforming to EN/IEC 61000-4-2
Shock resistance 98 m/s² for 11 ms
conversion time 1 ms per channel + 1 controller cycle time for analogue input analog input
Resistance to electromagnetic fields 10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
Surge withstand 2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5
2 kV relay output common mode conforming to EN/IEC 61000-4-5
1 kV I/O common mode conforming to EN/IEC 61000-4-5
1 kV shielded cable common mode conforming to EN/IEC 61000-4-5
0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5
1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5
1 kV relay output differential mode conforming to EN/IEC 61000-4-5
0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5
Supply (serial)serial link supply: 5 V, <200 mA
Protection type Without protection at 5 A
Transmission rate 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
480 Mbit/s for USB
Environment
Ambient air temp for storage/transportation -25…70 °C
ip degree of protection IP20 with protective cover in place
operating altitude 0...2000 m
Range of product Modicon M221
ambient air temperature for operation -10…55 °C (horizontal installation)
-10…35 °C (vertical installation)
Environmental characteristics Ordinary and hazardous location
Resistance to conducted disturbances 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
standards EN/IEC 60664-1
EN/IEC 61131-2
EN/IEC 61010-2-201
Storage altitude 0…3000 m
relative humidity 10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
electromagnetic emission Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011
Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011
Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to EN/IEC 55011
Regulation loop Adjustable PID regulator up to 14 simultaneous loops
vibration resistance 3.5 mm at 5…8.4 Hz on symmetrical rail
3.5 mm at 5…8.4 Hz on panel mounting
1 gn at 8.4…150 Hz on symmetrical rail
1 gn at 8.4…150 Hz on panel mounting
resistance to fast transients 2 kV (power lines) conforming to EN/IEC 61000-4-4
2 kV (relay output) conforming to EN/IEC 61000-4-4
1 kV (I/O) conforming to EN/IEC 61000-4-4
1 kV (Ethernet line) conforming to EN/IEC 61000-4-4
1 kV (serial link) conforming to EN/IEC 61000-4-4
resistance to magnetic fields 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
Recently viewed
230,23 € excl. VAT
280,88 € incl. VAT
Expected in 2-4 weeks