Main
Total inputs/outputs
14
product specific application
HVAC and pumping solution
Complementary
Product certifications
EAC
cURus
CSA
CE
Handle front plate colour
87 mm
Product or component type
Additional I/O module
[us] rated supply voltage
100...240 V +/- 10 % AC/DC
Analogue input number
3 analog input NTC/Pt 1000
2 configurable
Analogue input type
voltage 0...5 V (ratiometric)
voltage 0...10 V
NTC temperature probe - 50...100 °C - resolution: 0.1 °C
Pt 1000 temperature probe - 50...400 °C - resolution: 0.1 °C
current 0...20 mA/4...20 mA
voltage 0...1 V
Discrete output current
2 A for relay
Analogue output number
2 voltage, range: 0...10 V
2 PWM/PPM, range: 20 kHz, 12 V, 35 mA
1 current, range: 0...20 mA/4...20 mA
Discrete input logic
Sink or source (positive/negative)
width (w)
70.2 mm
Local signalling
1 LED (red) for programmable
1 LED (yellow) for programmable
1 LED (green) for programmable
Contacts usage
Volt-free contacts
Discrete input number
2
Net weight
0.385 kg
Realtime clock
Built-in clock at -10…55 °C
Discrete output number
1 for relay outputs SPDT with independent common
3 for relay outputs SPST with same common
Display type
Without display
Mounting support
DIN rail
depth
61.6 mm
Number of port
1 LAN expansion bus
Pollution degree
2
Power consumption in w
7 W
Sensor power supply
12 V DC at 85 mA
Input/output number
5 analog output(s)
4 digital output(s)
5 analog input(s)
Environment
Ambient air temp for storage/transportation
-20…85 °C
Directives
86/188/EEC - physical agents (noise) directive
2006/95/EC - low voltage directive
ip degree of protection
IP20
Range of product
Modicon M171/M172
ambient air temperature for operation
-10…55 °C conforming to UL 60730-1
overvoltage category
II
standards
EN/IEC 60730
relative humidity
10…90 % non-condensing