All categories
Compare Cart

STBDRC3210K - Standard digital output kit STB 24 V 115..230 V AC DC 2 O - Schneider Electric

Expected in 2-4 weeks
STBDRC3210K - Standard digital output kit STB 24 V 115..230 V AC DC 2 O - Schneider Electric - Standard digital output kit STB 24 V 115..230 V AC DC 2 O - Schneider Electric - 0
STBDRC3210K - Standard digital output kit STB 24 V 115..230 V AC DC 2 O - Schneider Electric
77,28 € excl. VAT
94,28 € incl. VAT
Text About:
Standard digital output kit STB 24 V 115..230 V AC DC 2 O - Schneider Electric
94,28 €
SPECIFICATIONS
Main
Discrete output logic Positive or negative
Discrete output voltage type AC
DC
switching capacity in va 600 VA resistive
Minimum load 50 mA
reset Manual reset COM fault
Complementary
product compatibility I/O base STBXBA2000
Power distribution module STBPDT3100/3105
Kit composition STBXTS2110, 5-terminal spring clamp connector
STBXTS1100, 5-terminal screw type connector
STBXBA3000 base
STBDRC3210 module
Product certifications FM Class 1 Division 2
CSA
UL
response time 5.25 ms off-to-on
6.75 ms on-to-off
Handle front plate colour 18.4 mm
Product or component type Standard digital output kit
[us] rated supply voltage 24 V DC
Current consumption 55 mA at 5 V DC for logic bus
marking CE
Discrete output function 2 NO/NC
Cold swapping Yes
Discrete output current 2000 mA
output voltage 20...250 V AC
5...30 V DC
width (w) 128.3 mm
Net weight 0.13 kg
Discrete output type Relay
Discrete output voltage 24 V
115...230 V
Fallback State 0 basic NIMs
User configurable standard NIMs
Insulation between channels 500 V for 1 minute
Discrete output number 2
depth 70 mm
Hot swapping Yes for standard NIMs
Insulation between channels and logic bus 1780 V for 1 minute
mechanical durability 1000000 cycles
electrical durability 100000 cycles resistive
Insulation between logic bus and actuator bus 1500 V for 1 minute
Pollution degree 2 conforming to IEC 60664-1
Surge current 20 A 10 ms capacitive
Shock resistance 30 gn for 11 ms conforming to IEC 88 reference 2-27
Status led 1 LED (green) module status (RDY)
1 LED per channel (green) channel status (OUT1 to OUT2)
1 LED (red) module error (ERR)
Supply Power distribution module
Protection type Coil protection integrated fuse on PDM time lag 10 A
Output surge protection GMOV
Environment
Ambient air temp for storage/transportation -40...185 °F without derating
ip degree of protection IP20 conforming to EN 61131-2 class 1
operating altitude <= 2000 m
Range of product Modicon STB distributed I/O solution
ambient air temperature for operation 32...140 °F without derating
overvoltage category II
standards EN/IEC 61131-2
relative humidity 95 % at 60 °C without condensation
vibration resistance 3 gn at 58…150 Hz on 35 x 7.5 mm symmetrical DIN rail
5 gn at 58…150 Hz on 35 x 15 mm symmetrical DIN rail
+/-0.35 mm at 10…58 Hz
Recently viewed
77,28 € excl. VAT
94,28 € incl. VAT
Expected in 2-4 weeks