Complementary
Absolute accuracy error
+/- 0.1 % of full scale 25 °C internal
+/- 0.15 % of full scale 25 °C external
absolute maximum input
+/- 7.5 V DC
product compatibility
Mounting base STBXBA1000
Power distribution module STBPDT3100/3105
Kit composition
STBART0200 module
STBXTS1100, 6-terminal screw type connector
STBXBA1000 base
STBXTS2100, 6-terminal spring clamp connector
Product certifications
UL
FM Class 1 Division 2
CSA
ATEX Cat 3G
C-Tick
data formats
EN 61131-2
IEC 61131-2
Product or component type
Standard analog input kit
[us] rated supply voltage
24 V DC
Current consumption
30 mA at 5 V DC for logic bus
marking
CE
Analogue input number
2
Analogue input type
Voltage +/- 80 mV
Temperature probe -100...+260 °C Cu 10 2, 3 or 4 wires IEC
Temperature probe -100...+450 °C Pt 100 2, 3 or 4 wires US/JIS
Temperature probe -100...+450 °C Pt 1000 2, 3 or 4 wires US/JIS
Temperature probe -200...+850 °C Pt 100 2, 3 or 4 wires IEC
Temperature probe -200...+850 °C Pt 1000 2, 3 or 4 wires IEC
Temperature probe -60...+180 °C Ni 100 2, 3 or 4 wires IEC
Temperature probe -60...+180 °C Ni 1000 2, 3 or 4 wires IEC
Thermocouple +130...+1820 °C thermocouple B
Thermocouple -200...+760 °C thermocouple J
Thermocouple -270...+1000 °C thermocouple E
Thermocouple -270...+1370 °C thermocouple K
Thermocouple -270...+400 °C thermocouple T
Thermocouple -50...+1665 °C thermocouple R
Thermocouple -50...+1665 °C thermocouple S
Cold swapping
Yes
addressing requirement
1 word for cold-junction compensation
2 input words
Fallback status
State 0 basic NIMs
User configurable standard NIMs
maximum wiring resistance
20 Ohm Cu 10 IEC/US/JIS 2 or 3 wires
20 Ohm Ni 100 IEC/US/JIS 2 or 3 wires
20 Ohm Pt 100 IEC/US/JIS 2 or 3 wires
200 Ohm Ni 1000 IEC/US/JIS 2 or 3 wires
200 Ohm Pt 1000 IEC/US/JIS 2 or 3 wires
50 Ohm Cu 10 IEC/US/JIS 4 wires
50 Ohm Ni 100 IEC/US/JIS 4 wires
50 Ohm Pt 100 IEC/US/JIS 4 wires
500 Ohm Ni 1000 IEC/US/JIS 4 wires
500 Ohm Pt 1000 IEC/US/JIS 4 wires
Hot swapping fallback
Yes for standard NIMs
measurement accuracy
+/- 1 °C Ni 100 25 °C external
+/- 1 °C Ni 100 25 °C internal
+/- 1 °C Ni 1000 25 °C external
+/- 1 °C Ni 1000 25 °C internal
+/- 1 °C Pt 100 25 °C internal
+/- 1 °C Pt 1000 25 °C internal
+/- 1.75 °C thermocouple B with external cold-junction compensation 25 °C
+/- 1.75 °C thermocouple E with external cold-junction compensation 25 °C
+/- 1.75 °C thermocouple J with external cold-junction compensation 25 °C
+/- 1.75 °C thermocouple K with external cold-junction compensation 25 °C
+/- 1.75 °C thermocouple R with external cold-junction compensation 25 °C
+/- 1.75 °C thermocouple S with external cold-junction compensation 25 °C
+/- 1.75 °C thermocouple T with external cold-junction compensation 25 °C
+/- 2 °C Pt 100 25 °C external
+/- 2 °C Pt 1000 25 °C external
+/- 2.85 °C thermocouple B with external cold-junction compensation 60 °C
+/- 2.85 °C thermocouple E with external cold-junction compensation 60 °C
+/- 2.85 °C thermocouple J with external cold-junction compensation 60 °C
+/- 2.85 °C thermocouple K with external cold-junction compensation 60 °C
+/- 2.85 °C thermocouple R with external cold-junction compensation 60 °C
+/- 2.85 °C thermocouple S with external cold-junction compensation 60 °C
+/- 2.85 °C thermocouple T with external cold-junction compensation 60 °C
+/- 3.6 °C thermocouple R with internal cold-junction compensation 25 °C
+/- 4 °C Cu 10 25 °C external
+/- 4 °C Cu 10 25 °C internal
+/- 4 °C thermocouple K with internal cold-junction compensation 25 °C
+/- 4.1 °C thermocouple S with internal cold-junction compensation 25 °C
+/- 4.2 °C thermocouple R with internal cold-junction compensation 60 °C
+/- 4.4 °C thermocouple T with internal cold-junction compensation 25 °C
+/- 4.6 °C thermocouple B with internal cold-junction compensation 25 °C
+/- 4.6 °C thermocouple E with internal cold-junction compensation 25 °C
+/- 5 °C thermocouple S with internal cold-junction compensation 60 °C
+/- 5.1 °C thermocouple J with internal cold-junction compensation 25 °C
+/- 5.5 °C thermocouple K with internal cold-junction compensation 60 °C
+/- 6.4 °C thermocouple T with internal cold-junction compensation 60 °C
+/- 6.8 °C thermocouple B with internal cold-junction compensation 60 °C
+/- 6.8 °C thermocouple E with internal cold-junction compensation 60 °C
+/- 7 °C thermocouple J with internal cold-junction compensation 60 °C
input impedance
10 MOhm +/- 80 mV
Measurement resolution
0.01 mV voltage
0.1 °C or 0.1 °F temperature probe
0.1 °C or 0.1 °F thermocouple
Insulation between channels and logic bus
1500 V for 1 minute
Maximum supply current for sensors
100 mA per input channels
Pollution degree
2 conforming to IEC 60664-1
Shock resistance
30 gn for 11 ms conforming to IEC 88 reference 2-27
conversion time
150 ms voltage 60 Hz
170 ms voltage 50 Hz
180 ms temperature probe 60 Hz 2 or 4 wires
200 ms temperature probe 50 Hz 2 or 4 wires
210 ms thermocouple with internal cold-junction compensation 60 Hz
230 ms thermocouple with internal cold-junction compensation 50 Hz
300 ms temperature probe 60 Hz 3 wires
340 ms temperature probe 50 Hz 3 wires
360 ms thermocouple with external cold-junction compensation 60 Hz
400 ms thermocouple with external cold-junction compensation 50 Hz
Status led
1 LED (green) module status (RDY)
1 LED (red) module error (ERR)
Supply
Power distribution module
Protection type
Short-circuit protection
Environment
Ambient air temp for storage/transportation
-40...185 °F without derating
ip degree of protection
IP20 conforming to EN 61131-2 class 1
operating altitude
<= 2000 m
Range of product
Modicon STB distributed I/O solution
ambient air temperature for operation
32...140 °F without derating
overvoltage category
II
relative humidity
95 % at 60 °C without condensation
vibration resistance
+/-0.35 mm at 10…58 Hz
3 gn at 58…150 Hz on 35 x 7.5 mm symmetrical DIN rail
5 gn at 58…150 Hz on 35 x 15 mm symmetrical DIN rail