All categories
Compare Cart

SR3B261JD - Modular smart relay, Zelio Logic, 26 I/O, 12 V DC, clock, display - Schneider Electric

Expected in 2-4 weeks
SR3B261JD - Modular smart relay, Zelio Logic, 26 I/O, 12 V DC, clock, display - Schneider Electric - Modular smart relay, Zelio Logic, 26 I/O, 12 V DC, clock, display - Schneider Electric - 0
SR3B261JD - Modular smart relay, Zelio Logic, 26 I/O, 12 V DC, clock, display - Schneider Electric - Modular smart relay, Zelio Logic, 26 I/O, 12 V DC, clock, display - Schneider Electric - 1
SR3B261JD - Modular smart relay, Zelio Logic, 26 I/O, 12 V DC, clock, display - Schneider Electric - Modular smart relay, Zelio Logic, 26 I/O, 12 V DC, clock, display - Schneider Electric - 2
SR3B261JD - Modular smart relay, Zelio Logic, 26 I/O, 12 V DC, clock, display - Schneider Electric - Modular smart relay, Zelio Logic, 26 I/O, 12 V DC, clock, display - Schneider Electric - 3
SR3B261JD - Modular smart relay, Zelio Logic, 26 I/O, 12 V DC, clock, display - Schneider Electric
244,99 € excl. VAT
298,89 € incl. VAT
Text About:
Modular smart relay, Zelio Logic, 26 I/O, 12 V DC, clock, display - Schneider Electric
298,89 €
SPECIFICATIONS
Main
Analogue input resolution 8 bits at maximum voltage
Discrete input current 4 mA
Maximum permissible voltage 14.4 V for analogue input circuit
maximum supply current 250 mA (without extension)
400 mA (with extensions)
reverse polarity protection With
Complementary
local display With
Product certifications C-Tick
UL
CSA
GL
GOST
response time 10 ms (from state 0 to state 1) for relay output
5 ms (from state 1 to state 0) for relay output
Analogue input range 0...12 V
0...10 V
Product or component type Modular smart relay
tightening torque 0.5 N.m
[uimp] rated impulse withstand voltage 4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1
[us] rated supply voltage 12 V
Connections - terminals Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid
Screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid
Screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end
current state 0 guaranteed <= 0.2 mA (IB...IG used as discrete input circuit)
<= 0.9 mA (I1...IA and IH...IR discrete input circuit)
output thermal current 5 A for 2 outputs for relay output
8 A for 8 outputs for relay output
Analogue input number 6
current state 1 guaranteed >= 2 mA (I1...IA and IH...IR discrete input circuit)
>= 0.5 mA (IB...IG used as discrete input circuit)
Operating distance 10 m between stations, with screened cable (sensor not isolated) for analogue input circuit
Analogue input type Common mode
Contacts type and composition NO for relay output
Clock With
clock drift 12 min/year at 0…55 °C
6 s/month at 25 °C
conversion error +/- 5 % at 25 °C for analogue input circuit
+/- 6.2 % at 55 °C for analogue input circuit
Discrete input type Resistive
number of outputs 10 relay
supply voltage limits 10.4…14.4 V
Discrete input voltage 12 V DC
Discrete input number 16 conforming to EN/IEC 61131-2 type 1
Disturbance radiated/conducted Class B conforming to EN 55022-11 group 1
Net weight 0.4 kg
counting frequency 1 kHz for discrete input
voltage state 1 guaranteed >= 7 V for IB...IG used as discrete input circuit
>= 5.6 V for I1...IA and IH...IR discrete input circuit
Immunity to microbreaks 1 ms repeated 20 times
input impedance 14 kOhm for IB...IG used as analogue input circuit
14 kOhm for IB...IG used as discrete input circuit
2.7 kOhm for I1...IA and IH...IR discrete input circuit
switching capacity in ma >= 10 mA at 12 V (relay output)
mechanical durability 10000000 cycles for relay output
power dissipation in w 3 W without extension
5 W with extensions
backup time 10 years at 25 °C
electrical durability AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to EN/IEC 60947-5-1
DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to EN/IEC 60947-5-1
output voltage limits 24...250 V AC (relay output)
5...30 V DC (relay output)
repeat accuracy +/- 2 % at 55 °C for analogue input circuit
voltage state 0 guaranteed <= 3 V for IB...IG used as discrete input circuit
<= 2.4 V for I1...IA and IH...IR discrete input circuit
Pollution degree 2 conforming to EN/IEC 61131-2
Maximum altitude transport 3048 m
Input compatibility 3-wire proximity sensors PNP for discrete input
Lsb value 39 mV for analogue input circuit
conversion time Smart relay cycle time for analogue input circuit
cycle time 6…90 ms
Number or control scheme lines 0…500 with FBD programming
0…240 with ladder programming
Operating rate in hz 0.1 Hz (at Ie) for relay output
10 Hz (no load) for relay output
checks Program memory on each power up
Environment
Ambient air temp for storage/transportation -40…70 °C
ip degree of protection IP20 (terminal block) conforming to IEC 60529
IP40 (front panel) conforming to IEC 60529
operating altitude 2000 m
Range of product Zelio Logic
ambient air temperature for operation -20…40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2
-20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2
Environmental characteristics EMC directive conforming to EN/IEC 61000-6-2
EMC directive conforming to EN/IEC 61000-6-3
EMC directive conforming to EN/IEC 61000-6-4
EMC directive conforming to EN/IEC 61131-2 zone B
Low voltage directive conforming to EN/IEC 61131-2
overvoltage category III conforming to EN/IEC 60664-1
standards EN/IEC 60068-2-6 Fc
EN/IEC 61000-4-12
EN/IEC 61000-4-3
EN/IEC 61000-4-6 level 3
EN/IEC 61000-4-5
EN/IEC 61000-4-11
EN/IEC 61000-4-2 level 3
EN/IEC 60068-2-27 Ea
EN/IEC 61000-4-4 level 3
relative humidity 95 % without condensation or dripping water