Complementary
local display
With
Product certifications
GL
CSA
UL
GOST
C-Tick
response time
10 ms (from state 0 to state 1) for relay output
5 ms (from state 1 to state 0) for relay output
Analogue input range
0...10 V
0...24 V
Product or component type
Compact smart relay
tightening torque
0.5 N.m
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1
[us] rated supply voltage
24 V DC
Connections - terminals
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid
Screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid
Screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end
current state 0 guaranteed
<= 0.5 mA (IB...IG used as discrete input circuit)
<= 0.75 mA (I1...IA and IH...IR discrete input circuit)
output thermal current
8 A for all 4 outputs for relay output
Analogue input number
4
current state 1 guaranteed
>= 1.2 mA (IB...IG used as discrete input circuit)
>= 2.2 mA (I1...IA and IH...IR discrete input circuit)
Operating distance
10 m between stations, with screened cable (sensor not isolated) for analogue input circuit
Analogue input type
Common mode
Contacts type and composition
NO for relay output
Clock
With
clock drift
12 min/year at 0…55 °C
6 s/month at 25 °C
conversion error
+/- 5 % at 25 °C for analogue input circuit
+/- 6.2 % at 55 °C for analogue input circuit
Discrete input type
Resistive
number of outputs
4 relay
supply voltage limits
19.2…30 V
Discrete input voltage
24 V DC
Discrete input number
8 conforming to EN/IEC 61131-2 type 1
Disturbance radiated/conducted
Class B conforming to EN 55022-11 group 1
Net weight
0.25 kg
counting frequency
1 kHz for discrete input
voltage state 1 guaranteed
>= 15 V for I1...IA and IH...IR discrete input circuit
>= 15 V for IB...IG used as discrete input circuit
Immunity to microbreaks
1 ms
input impedance
12 kOhm for IB...IG used as analogue input circuit
12 kOhm for IB...IG used as discrete input circuit
7.4 kOhm for I1...IA and IH...IR discrete input circuit
switching capacity in ma
>= 10 mA at 12 V (relay output)
mechanical durability
10000000 cycles for relay output
power dissipation in w
3 W without extension
backup time
10 years at 25 °C
electrical durability
AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to EN/IEC 60947-5-1
DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to EN/IEC 60947-5-1
output voltage limits
24...250 V AC (relay output)
5...30 V DC (relay output)
repeat accuracy
+/- 2 % at 55 °C for analogue input circuit
voltage state 0 guaranteed
<= 5 V for I1...IA and IH...IR discrete input circuit
<= 5 V for IB...IG used as discrete input circuit
Pollution degree
2 conforming to EN/IEC 61131-2
Maximum altitude transport
3048 m
Input compatibility
3-wire proximity sensors PNP for discrete input
Lsb value
39 mV for analogue input circuit
conversion time
Smart relay cycle time for analogue input circuit
cycle time
6…90 ms
Number or control scheme lines
0…240 with ladder programming
0…500 with FBD programming
Operating rate in hz
0.1 Hz (at Ie) for relay output
10 Hz (no load) for relay output
Temperature probe type
NTC 10k at 25 °C
NTC 1000k at 25 °C
KTY81 210/220/221/222/250
Pt 500
checks
Program memory on each power up
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 (terminal block) conforming to IEC 60529
IP40 (front panel) conforming to IEC 60529
operating altitude
2000 m
Range of product
Zelio Logic
ambient air temperature for operation
-20…40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2
-20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2
Environmental characteristics
EMC directive conforming to EN/IEC 61000-6-2
EMC directive conforming to EN/IEC 61000-6-3
EMC directive conforming to EN/IEC 61000-6-4
EMC directive conforming to EN/IEC 61131-2 zone B
Low voltage directive conforming to EN/IEC 61131-2
overvoltage category
III conforming to EN/IEC 60664-1
standards
EN/IEC 61000-4-12
EN/IEC 61000-4-4 level 3
EN/IEC 61000-4-5
EN/IEC 61000-4-11
EN/IEC 61000-4-2 level 3
EN/IEC 60068-2-6 Fc
EN/IEC 61000-4-6 level 3
EN/IEC 60068-2-27 Ea
EN/IEC 61000-4-3
relative humidity
95 % without condensation or dripping water