Additional Information
type of order
Break switch
type of pole
3 P
Main
Number of modules
3
rated operational voltage ue
400 V
Neutral position
without neutral
Complementary
acceptable current rating with ac22 category a
80 A
cage clamp position
in line
connection cross-sect. flexible conductor
6 / 35mm²
depth of installed product
68 mm
electrical durability at nominal load in ac21in operating cycles
2500
power loss per pole at in
2.7 W
[in] rated current
80 A
acceptable current rating with ac22 category b
80 A
connection cross-sect. rigid cable
6 / 50mm²
degree of pollution according to iec 60664 / iec 60947-2
2
electrical durability at nominal load in ac22 in operating cycles
2500
height of installed product
83 mm
number of mechanical operations
40000
quantity of no contacts
3
total power loss under in
8.1 W
type of connection
with screw
type of voltage input 1
AC
width of installed product
52.5 mm
storage/transport temperature
-40…80 °C
thermal rated current outside of housings
80 A
tightening torque
3,6Nm
Rated insulation voltage
440 V
rated operational current in ac21 category a
80 A
rated operational current in ac21category b
80 A
rated short-time withstand current 1s
0.96 kA
frequency
50 to 60 Hz
rated impulse withstand voltage
6000 V
Poles description
3 P
Environment
altitude
2000 m
european directive weee
concerned
protection index ip
IP20
standard text
IEC 60947-3
operating temperature
-20…50 °C