Complementary
[ie] rated operational current
3 A at 28 V (DC) NC conforming to IEC
3 A at 250 V (AC) NC conforming to IEC
6 A at 28 V (DC) NO conforming to IEC
6 A at 250 V (AC) NO conforming to IEC
6 A at 277 V (AC) conforming to UL
8 A at 30 V (DC) conforming to UL
Control type
Lockable test button
Product certifications
CE
UL
CSA
EAC
Lloyd's
Product or component type
Pre-assembled plug-in relay with socket
[uimp] rated impulse withstand voltage
2.5 kV during 1.2/50 µs
minimum switching capacity
170 mW at 10 mA, 17 V
Connections - terminals
Connector, 1 x 0.25...1 x 2.5 mm² (AWG 22...AWG 14) flexible with cable end
Connector, 2 x 0.25...2 x 1 mm² (AWG 22...AWG 17) flexible with cable end
Connector, 1 x 0.5...1 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Connector, 2 x 0.5...2 x 1.5 mm² (AWG 20...AWG 16) solid without cable end
minimum switching current
10 mA
protection category
RT I
average coil consumption
1.2 W, AC
Cad overall depth
80.35 mm
Contacts material
AgNi
Cad overall height
82.8 mm
Contacts type and composition
4 C/O
safety reliability data
B10d = 100000
Cad overall width
26.9 mm
Sale per indivisible quantity
30
Net weight
0.105 kg
Operating position
Any position
test levels
Level A group mounting
mechanical durability
10000000 cycles
Rated operational voltage limits
19.2...26.4 V AC
continuous output current
5 A
electrical durability
100000 cycles for resistive load
Device presentation
Complete product
average coil resistance
180 Ohm at 20 °C +/- 10 %
Pollution degree
2
drop-out voltage threshold
>= 0.3 Uc AC
Maximum switching capacity
1500 VA/168 W AC/DC
minimum switching voltage
17 V
Maximum switching voltage
250 V
torque value
1 N.m
dielectric strength
1300 V AC between contacts with micro disconnection
2000 V AC between coil and contact with basic insulation
2000 V AC between poles with basic insulation
Operate time
20 ms
Operating rate
<= 1200 cycles/hour under load
<= 18000 cycles/hour no-load
Shock resistance
10 gn for in operation
30 gn for not operating
Release time
20 ms
Resistive rated load
6 A at 250 V AC
6 A at 28 V DC
Status led
Without
Utilisation coefficient
20 %
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20 conforming to EN/IEC 60529
Range of product
Harmony Electromechanical Relays
ambient air temperature for operation
-40…55 °C
standards
UL 508
EN/IEC 61810-1
CSA C22.2 No 14
IEC 61984
vibration resistance
3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation
5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating