Main
Device short name
RXG
[ithe] thermal current under enclosure
5 A at -40…55 °C
[uc] control circuit voltage
220 V AC 50/60 Hz
[ui] rated insulation voltage
250 V conforming to IEC
300 V conforming to CSA
300 V conforming to UL
Series name
Interface relay
Complementary
[ie] rated operational current
5 A at 30 V (DC) conforming to UL
5 A at 30 V (DC) conforming to IEC
5 A at 250 V (AC) conforming to IEC
5 A at 250 V (AC) conforming to UL
Product certifications
CSA
EAC
CE
UL
DNV-GL
Product or component type
Plug-in relay
[uimp] rated impulse withstand voltage
6 kV 1.2/50 µs
minimum switching capacity
50 mW at 10 mA, 5 V DC
protection category
RT I
coil insulation class
Class F
Average consumption in va
0.82 VA 60 Hz
Contacts material
Silver alloy (AgSnO2In2O3)
Contacts type and composition
2 C/O
safety reliability data
B10d = 100000
Control circuit voltage limits
0.8...1.1 Uc AC
Load current
5 A at 250 V AC
Colour of cover
Standard
Local signalling
Flag
Net weight
0.02 kg
test levels
Level A group mounting
mechanical durability
10000000 cycles
electrical durability
100000 cycles for NO resistive load at 55 °C
100000 cycles for NC resistive load at 55 °C
Device presentation
Complete product
Pollution degree
2
drop-out voltage threshold
>= 0.3 Uc AC
Maximum switching capacity
1250 VA
mounting position
Any position
coil resistance
21000 Ohm +/- 15 %
Maximum contact resistance
100 mOhm
Maximum switching voltage
250 V AC
30 V DC
torque value
0.8 N.m
dielectric strength
1000 V AC between contacts with micro disconnection
5000 V AC between coil and contact with reinforced insulation
3000 V AC between poles with basic insulation
Operate time
20 ms
Operating rate
<= 1800 cycles/hour under load
<= 18000 cycles/hour no-load
Shock resistance
20 gn in operation
100 gn not in operation
Release time
20 ms
Status led
With
Utilisation coefficient
20 %
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP40
Range of product
Harmony Electromechanical Relays
ambient air temperature for operation
-40…70 °C
overvoltage category
III
standards
IEC 61810-1
CSA C22.2 No 14
UL 508
relative humidity
10…85 %
vibration resistance
3 gn, amplitude = +/- 0.75 mm (f = 10…150 Hz)in operation
5 gn, amplitude = +/- 0.75 mm (f = 10…150 Hz)not in operation
insulation resistance
1000 MOhm at 500 V DC