Main
Device short name
RXG
[ithe] thermal current under enclosure
10 A
[uc] control circuit voltage
230 V AC 50/60 Hz
[ui] rated insulation voltage
250 V conforming to IEC
Series name
Interface relay
Complementary
[ie] rated operational current
10 A at 30 V (DC) conforming to UL
10 A at 30 V (DC) conforming to IEC
10 A at 250 V (AC) conforming to IEC
10 A at 250 V (AC) conforming to UL
Control type
Lockable test button
Product certifications
EAC
CSA
UL
CE
DNV-GL
Product or component type
Pre-assembled plug-in relay with socket
[uimp] rated impulse withstand voltage
6 kV 1.2/50 µs between coil and contact
1.2 kV 1.2/50 µs between contacts
2.5 kV 1.2/50 µs between terminals and LTB area
1.5 kV 1.2/50 µs between terminals and base
minimum switching capacity
500 mW at 100 mA, 5 V DC
Connections - terminals
Connector, 1 x 0.25...1 x 2.5 mm² (AWG 22...AWG 14) flexible with cable end
Connector, 2 x 0.25...2 x 1 mm² (AWG 22...AWG 17) flexible with cable end
Connector, 1 x 0.5...1 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Connector, 2 x 0.5...2 x 1.5 mm² (AWG 20...AWG 16) solid without cable end
protection category
RT I
coil insulation class
Class F
average coil consumption
0.96 VA AC 50...60 Hz
Contacts material
Silver alloy (AgSnO2In2O3)
Contacts type and composition
1 C/O
safety reliability data
B10d = 100000
Load current
10 A
Colour of cover
Transparent
Net weight
0.058 kg
test levels
Level A group mounting
mechanical durability
10000000 cycles
electrical durability
100000 cycles resistive load
Device presentation
Complete product
Pollution degree
2
drop-out voltage threshold
>= 0.3 Uc AC
Maximum switching capacity
2500 VA AC
300 W DC
mounting position
Any position
coil resistance
23500 Ohm +/- 15 %
Maximum contact resistance
100 mOhm
Maximum switching voltage
250 V
torque value
0.8 N.m
0.79 N.m
dielectric strength
1000 V AC between contacts with micro disconnection
1300 V between terminals and base with basic insulation
3000 V between terminals and LTB area with basic insulation
5000 V AC between coil and contact with reinforced insulation
Operate time
20 ms
Operating rate
<= 1800 cycles/hour under load
<= 18000 cycles/hour no-load
Shock resistance
20 gn in operation
100 gn not in operation
Release time
20 ms
Status led
With
Utilisation coefficient
20 %
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20
Range of product
Harmony Electromechanical Relays
ambient air temperature for operation
-40…70 °C
overvoltage category
III
standards
IEC 61810-1
CSA C22.2 No 14
UL 508
IEC 61984
relative humidity
10…85 %
vibration resistance
3 gn, amplitude = +/- 1.5 mm (f = 10…150 Hz)in operation
5 gn, amplitude = +/- 1.5 mm (f = 10…150 Hz)not in operation
insulation resistance
1000 MOhm at 500 V DC