												[ithe] thermal current under enclosure
												10 A at -40…55 °C
											
                            
																					
												[uc] control circuit voltage
												24 V AC 50/60 Hz
											
                            
																					
												[ui] rated insulation voltage
												250 V conforming to IEC
300 V conforming to CSA
300 V conforming to UL
											
                            
																					
												Series name
												Universal
											
                            
																			 
																	
										Complementary
																					
												[ie] rated operational current
												10 A at 277 V AC conforming to UL
10 A at 30 V DC conforming to UL
10 A at 277 V AC (same polarity) conforming to CSA
10 A at 30 V DC conforming to CSA
5 A at 250 V AC (NC) conforming to IEC
5 A at 28 V DC (NC) conforming to IEC
10 A at 250 V AC (NO) conforming to IEC
10 A at 28 V DC (NO) conforming to IEC
											
                            
																					
												Control type
												Without lockable test button
											
                            
																					
												Product certifications
												CSA
UL
EAC
											
                            
																					
												Product or component type
												Plug-in relay
											
                            
																					
												[uimp] rated impulse withstand voltage
												4 kV (1.2/50 µs)
											
                            
																					
												minimum switching capacity
												170 mW at 10 mA, 17 V
											
                            
																					
												protection category
												RT I
											
                            
																					
												average coil consumption in va
												3 at 60 Hz
											
                            
																					
												Contacts material
												AgNi
											
                            
																					
												Contacts type and composition
												3 C/O
											
                            
																					
												safety reliability data
												B10d = 100000
											
                            
																					
												Net weight
												0.086 kg
											
                            
																					
												Operating position
												Any position
											
                            
																					
												test levels
												Level A group mounting
											
                            
																					
												mechanical durability
												5000000 cycles
											
                            
																					
												Rated operational voltage limits
												19.2...26.4 V AC
											
                            
																					
												electrical durability
												100000 cycles for resistive load
											
                            
																					
												Device presentation
												Complete product
											
                            
																					
												average coil resistance
												72 Ohm at 20 °C +/- 15 %
											
                            
																					
												Pollution degree
												2
											
                            
																					
												drop-out voltage threshold
												>= 0.15 Uc AC
											
                            
																					
												Shape of pin
												Cylindrical
											
                            
																					
												Maximum switching capacity
												2500 VA/280 W
											
                            
																					
												Maximum switching voltage
												250 V conforming to IEC
											
                            
																					
												dielectric strength
												1500 V AC between contacts with micro disconnection
2500 V AC between coil and contact with reinforced
2000 V AC between poles with basic
											
                            
																					
												Operate time
												20 ms at nominal voltage
											
                            
																					
												Operating rate
												<= 18000 cycles/hour no-load
<= 1200 cycles/hour under load
											
                            
																					
												Shock resistance
												10 gn (duration = 11 ms) for in operation conforming to EN/IEC 60068-2-27
10 gn (duration = 11 ms) for not operating conforming to EN/IEC 60068-2-27
											
                            
																					
												Release time
												20 ms at nominal voltage
											
                            
																					
												Resistive rated load
												10 A at 250 V AC
10 A at 28 V DC
											
                            
																					
												Status led
												With
											
                            
																					
												Utilisation coefficient
												20 %
											
                            
																			 
																	
										Environment
																					
												Ambient air temp for storage/transportation
												-40…85 °C
											
                            
																					
												ip degree of protection
												IP40
											
                            
																					
												Range of product
												Harmony Electromechanical Relays
											
                            
																					
												ambient air temperature for operation
												-40…55 °C
											
                            
																					
												standards
												EN/IEC 61810-1
UL 508
CSA C22.2 No 14
											
                            
																					
												vibration resistance
												3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation