Complementary
[ie] rated operational current
6 A 1 C/O (AC-1/DC-1) conforming to IEC/UL
Average resistance
20500 Ohm network: DC at 23 °C +/- 10 %
Control type
Without push-button
Product certifications
GOST
CSA
UL
Handle front plate colour
78.6 mm
Product or component type
Pre-assembled plug-in relay with socket
[uimp] rated impulse withstand voltage
6 kV conforming to IEC
minimum switching capacity
120 mW
Connections - terminals
Spring terminals, 1 x 0.2...1 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Spring terminals, 1 x 0.2...1 x 1.5 mm² (AWG 24...AWG 16) solid without cable end
minimum switching current
100 mA
protection category
RT III
marking
CE
reset time
20 ms
average coil consumption
0.17 W, DC
Contact terminal arrangement
Separate
Contacts material
Silver alloy (AgSnO2)
contact operation
Standard
Contacts type and composition
1 C/O
Fixing mode
Plastic compression spring
safety reliability data
B10d = 60000
Load current
6 A at 250 V AC 0.5 mm mounting distance
Sale per indivisible quantity
10
width (w)
6.2 mm
Net weight
0.029 kg
clamping force
10…40 N
Operating position
Any position
test levels
Level A group mounting
Mounting support
35 mm symmetrical DIN rail
depth
101 mm
mechanical durability
10000000 cycles
electrical durability
60000 cycles for resistive load, 6 A at 250 V, AC-1
Device presentation
Complete product
drop-out voltage threshold
>= 0.05 Uc
operating time
5 ms reset
12 ms
Shape of pin
Flat (PCB type)
input voltage
230 V AC/DC (input voltage limit: 184...264.5 V)
Maximum switching capacity
1500 VA
150 W
minimum switching voltage
12 V
Maximum switching voltage
277 V
dielectric strength
1000 V AC between contacts
4000 V AC between coil and contact
Operating rate
<= 72000 cycles/hour no-load
<= 360 cycles/hour under load
Shock resistance
10 gn (duration = 11 ms) for in operation conforming to EN/IEC 60068-2-27
5 gn (duration = 11 ms) for not operating conforming to EN/IEC 60068-2-27
Status led
With
Terminals description iso n°1
(A1-A2)CO
(11-12-14)OC
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP40 conforming to EN/IEC 60529
Range of product
Harmony Electromechanical Relays
ambient air temperature for operation
-40…70 °C
standards
CSA C22.2 No 14
EN/IEC 61810-1
UL 508
vibration resistance
10 gn, amplitude = +/- 1 mm (f = 10…150 Hz)10 cycles not operating conforming to EN/IEC 60068-2-6
5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)10 cycles in operation conforming to EN/IEC 60068-2-6