Complementary
[ie] rated operational current
16 A (AC-1/DC-1) NO conforming to IEC
8 A (AC-1/DC-1) NC conforming to IEC
[ue] rated operational voltage
8.4...18 V DC
Control type
Without push-button
Product certifications
EAC
UL
CSA
Product or component type
Plug-in relay
[uimp] rated impulse withstand voltage
3.6 kV conforming to IEC 61000-4-5
minimum switching capacity
120 mW at 10 mA, 12 V
minimum switching current
10 mA
protection category
RT I
average coil consumption
0.45 W DC
Contacts material
Silver alloy (AgNi)
contact operation
Standard
Contacts type and composition
1 C/O
safety reliability data
B10d = 100000
Sale per indivisible quantity
10
Net weight
0.014 kg
Operating position
Any position
test levels
Level A group mounting
mechanical durability
30000000 cycles
electrical durability
100000 cycles, 16 A at 250 V, AC-1 NO
100000 cycles, 8 A at 250 V, AC-1 NC
Device presentation
Complete product
average coil resistance
360 Ohm network: AC at 20 °C +/- 10 %
drop-out voltage threshold
>= 0.1 Uc DC
operating time
20 ms operating
20 ms reset
Shape of pin
Flat (PCB type)
Maximum switching capacity
4000 VA/448 W
minimum switching voltage
12 V
Maximum switching voltage
300 V DC conforming to IEC
dielectric strength
1000 V AC between contacts
2500 V AC between poles
5000 V AC between coil and contact
Operating rate
<= 600 cycles/hour under load
<= 18000 cycles/hour no-load
Shock resistance
10 gn (duration = 11 ms) for not operating conforming to EN/IEC 60068-2-27
5 gn (duration = 11 ms) for in operation conforming to EN/IEC 60068-2-27
Resistive rated load
16 A at 250 V AC
16 A at 28 V DC
Status led
Without
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP40 conforming to EN/IEC 60529
Range of product
Harmony Electromechanical Relays
ambient air temperature for operation
-40…85 °C (DC)
standards
CSA C22.2 No 14
EN/IEC 61810-1
UL 508
vibration resistance
+/- 1 mm (f= 10…55 Hz) conforming to EN/IEC 60068-2-6