Main
Device short name
RPF
[ithe] thermal current under enclosure
25 A at -40…55 °C relays side by side without a gap
30 A at -40…55 °C 13 mm gap between two relays
[uc] control circuit voltage
12 V DC
[ui] rated insulation voltage
250 V conforming to IEC
300 V conforming to UL
Series name
Power
Complementary
[ie] rated operational current
30 A at 277 V (AC) NO conforming to UL
20 A at 28 V (DC) NO conforming to UL
30 A at 250 V (AC) NO conforming to IEC
25 A at 28 V (DC) NO conforming to IEC
3 A at 277 V (AC) NC conforming to UL
3 A at 28 V (DC) NC conforming to UL
3 A at 250 V (AC) NC conforming to IEC
3 A at 28 V (DC) NC conforming to IEC
Average resistance
86 Ohm at 20 °C +/- 10 %
Control type
Without lockable test button
Product certifications
CE
CSA
GOST
UL
Product or component type
DIN rail/panel mount relay
[uimp] rated impulse withstand voltage
4 kV during 1.2/50 µs
protection category
RT II
average coil consumption
1.7 W
Cad overall depth
39.2 mm
Contacts material
Silver tin oxide
Cad overall height
68.5 mm
Contacts type and composition
2 C/O
safety reliability data
B10d = 100000
Cad overall width
33.7 mm
Control circuit voltage limits
9.6...13.2 V
Net weight
0.082 kg
Operating position
Any position
test levels
Level A group mounting
Mounting support
DIN rail
Panel
mechanical durability
5000000 cycles
electrical durability
100000 cycles for resistive load
Device presentation
Complete product
Pollution degree
3
drop-out voltage threshold
>= 0.1 Uc
Shape of pin
Flat
Maximum switching capacity
7500 VA/700 W
Maximum switching voltage
250 V conforming to IEC
Minimum recommended switching capacity
6000 mW 500 mA / 12 V for NO
170 mW 10 mA / 6 V for NC
dielectric strength
2000 V AC between poles with basic
4000 V AC between coil and contact with reinforced
1500 V AC between contacts with micro disconnection
Operate time
25 ms
Operating rate
<= 1200 cycles/hour under load
<= 18000 cycles/hour no-load
Shock resistance
10 gn for in operation
30 gn for not operating
Release time
25 ms
Resistive rated load
25 A at 28 V DC
30 A at 250 V AC
Utilisation coefficient
10 %
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP40 conforming to EN/IEC 60529
Range of product
Harmony Electromechanical Relays
ambient air temperature for operation
-40…55 °C
standards
UL 508
CSA C22.2 No 14
EN/IEC 61810-1
vibration resistance
3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation
10 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating