Main
[ui] rated insulation voltage
2 kV
Complementary
Product certifications
UL
GL
CSA
Product or component type
Voltage/current converter
tightening torque
0.6…1.1 N.m
[us] rated supply voltage
24 V DC +/- 20 %, isolated
Current consumption
<= 70 mA for voltage output
<= 90 mA for current output
abnormal analog output current
-30…0 mA, output selected 0...20 mA no input or input wire broken
4…30 mA, output selected 4...20 mA no input or input wire broken
marking
CE
temperature coefficient
200 ppm/°C
Analogue input type
Voltage 0...300 V AC/DC 50/60 Hz
Voltage 0...50 V AC/DC 50/60 Hz
Voltage 0...500 V AC/DC 50/60 Hz
Clamping connection capacity
1 x 2.5 mm²
2 x 1.5 mm²
Fixing mode
By screws (mounting plate)
Clip-on (35 mm symmetrical DIN rail)
safety reliability data
MTTFd = 21.6 years
B10d = 20000
Analogue output type
Current 0...20 mA <= 500 Ohm switchable
Current 4...20 mA <= 500 Ohm switchable
Voltage 0...10 V >= 100 kOhm switchable
Local signalling
LED (green) for power ON
Disturbance radiated/conducted
CISPR 11
CISPR 22 group 1 - class B
Net weight
0.15 kg
measurement error
+/- 10 % of full scale at 20 °C (electromagnetic interference of 10 V/m)
+/- 5 % of full scale at 20 °C
abnormal analog output voltage
-15...0 V no input or input wire broken
repeat accuracy
+/- 0.2 % full scale at 20 °C
+/- 0.6 % full scale at 60 °C
Pollution degree
2 conforming to IEC 60664-1
Resistance to electrostatic discharge
6 kV (in contact) conforming to IEC 61000-4-2 level 3
8 kV (in air) conforming to IEC 61000-4-2 level 3
Shock resistance
50 gn for 11 ms conforming to IEC 60068-2-27
Surge withstand
0.5 kV during 1.2/50 µs conforming to IEC 61000-4-5
Protection type
Short-circuit protection on output
Reverse polarity protection on output
Overvoltage protection on output (+/- 30 V)
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20 (terminal block)
IP50 (housing)
Range of product
Harmony Analog
ambient air temperature for operation
0…50 °C mounting side by side
0…60 °C 2 cm spacing
standards
IEC 60584-1
IEC 60947-1
fire resistance
850 °C conforming to IEC 60695-2-1
850 °C conforming to UL
vibration resistance
5 gn (f= 10…100 Hz) conforming to IEC 60068-2-6
resistance to fast transients
1 kV (on input-output) conforming to IEC 61000-4-4
2 kV (on power supply) conforming to IEC 61000-4-4