Relay monitored parameters
Detection by discrete sensors
switching capacity in va
1250 VA
Relay type
Level control relay
relay name
RM35L
[ui] rated insulation voltage
250 V conforming to IEC 60664-1
Complementary
[un] rated nominal voltage
24...240 V AC/DC 50/60 Hz +/- 10 %
power consumption
1.5 W DC
cable capacity
10 nF for probe cable
maximum switching current
5 A AC/DC
Product certifications
GOST
CSA
UL
GL
C-Tick
output contacts
1 C/O
Product or component type
Level control relay
tightening torque
0.6…1 N.m conforming to IEC 60947-1
Connections - terminals
Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
minimum switching current
10 mA at 5 V DC
marking
CE : EMC 89/336/EEC
CE : 73/23/EEC
reset time
1000 ms
4000 ms
Delay at power up
0.5 s
Contacts type and composition
2 C/O
safety reliability data
B10d = 170000
MTTFd = 182.6 years
width (w)
35 mm
supply voltage limits
20.4…264 V AC/DC
Local signalling
LED (yellow) for relay ON
LED (green) for power ON
LED (yellow) for timer ON
measurement error
0.5 %/°C with temperature variation
measurement accuracy
+/- 10 % of the full scale value
+/- 20 % for the HS range
Operating position
Any position without derating
Immunity to microbreaks
100 ms DC
90 ms AC
Mounting support
35 mm symmetrical DIN rail conforming to EN/IEC 60715
Maximum supply current for sensors
40 mA
mechanical durability
30000000 cycles
electrical durability
100000 cycles
repeat accuracy
+/- 2 % for time delay
Housing material
Self-extinguishing plastic
Pollution degree
3 conforming to IEC 60664-1
Maximum switching voltage
250 V AC/DC
sensitivity adjustment
5…100 %
Operating rate
<= 360 operations/hour full load
operating voltage tolerance
- 15 % + 10 % Un
Utilisation category
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
Nominal output current
5 A
Time delay
Adjustable 0.1...5 s, +/- 10 %
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
Range of product
Harmony Control Relays
ambient air temperature for operation
-20…50 °C
electromagnetic compatibility
Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
overvoltage category
III conforming to IEC 60664-1
standards
EN/IEC 60255-6
relative humidity
95 % at 55 °C conforming to IEC 60068-2-30
dielectric test voltage
2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
2 kV, 1 min AC 50 Hz conforming to IEC 60664-1
insulation resistance
> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5
> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1