Complementary
Adjustment of asymmetry threshold
5...15 % of Un selected
maximum switching current
8 A AC
Product certifications
GL
EAC
CCC
CE
CSA
UL
RCM
response time
<= 300 ms
output contacts
2 C/O
Product or component type
3-phase control relay
tightening torque
0.6…1 N.m conforming to IEC 60947-1
[us] rated supply voltage
380...480 V AC
Connections - terminals
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
minimum switching current
10 mA at 5 V DC
reset time
1500 ms at maximum voltage
Contacts material
Cadmium free
hysteresis
2 % fixed of selectable
Contacts type and composition
2 C/O
safety reliability data
MTTFd = 388.1 years
B10d = 350000
maximum measuring cycle
150 ms measurement cycle as true rms value
width (w)
22.5 mm
supply voltage limits
304…576 V AC
supply voltage frequency
50...60 Hz +/- 10 %
switching threshold drift
<= 0.05 % per degree centigrade depending permissible ambient air temperature
<= 1 % within the supply voltage range
Net weight
0.09 kg
measurement error
< 1 % over the whole range with voltage variation
< 0.05 %/°C with temperature variation
operating limits
- 20 % + 20 % Un
Immunity to microbreaks
10 ms
Mounting support
35 mm DIN rail conforming to EN/IEC 60715
mechanical durability
10000000 cycles
electrical durability
100000 cycles
repeat accuracy
+/- 0.5 % for input and measurement circuit
+/- 3 % for time delay
Housing material
Self-extinguishing plastic
Pollution degree
3 conforming to IEC 60664-1
3 conforming to UL 508
Power consumption in va
15 VA at 480 V AC 60 Hz
mounting position
Any position
Network number of phases
3 phases
Maximum switching voltage
250 V AC
voltage detection threshold
< 100 V AC
Shock resistance
15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27
5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
Run-up delay at power-up
650 ms
Status led
LED (yellow) relay ON
LED (green) power ON
Setting accuracy of the switching threshold
+/- 10 % of the full scale
Utilisation category
AC-15 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
AC-1 conforming to IEC 60947-4-1
DC-1 conforming to IEC 60947-4-1
Setting accuracy of time delay
10 P
Threshold adjustment voltage
2...20 % of Un selected
Time delay drift
<= 0.05 % per degree centigrade depending permissible ambient air temperature
<= 1 % within the supply voltage range
Time delay type
Adjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
Voltage range
380...480 V phase to phase
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 (terminals) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529
Range of product
Harmony Control Relays
ambient air temperature for operation
-20…50 °C at 60 Hz
-20…60 °C at 50 Hz AC/DC
electromagnetic compatibility
Immunity for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-1
Immunity for industrial environments conforming to EN/IEC 61000-6-2
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4
Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5
Conducted and radiated emissions class B group 1 conforming to CISPR 11
Conducted and radiated emissions class B conforming to CISPR 22
overvoltage category
III conforming to IEC 60664-1
III conforming to UL 508
standards
EN/IEC 60255-1
relative humidity
93…97 % at 25…55 °C conforming to IEC 60068-2-30
vibration resistance
0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6
1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6
0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
dielectric test voltage
2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27
insulation resistance
> 100 MOhm at 500 V DC conforming to IEC 60255-27