All categories
Compare Cart

RM17TG20 - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric

2 In stock EAN: 3389119405072
RM17TG20 - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - 0
RM17TG20 - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - 1
RM17TG20 - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - 2
RM17TG20 - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - 3
RM17TG20 - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - 4
RM17TG20 - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - 5
RM17TG20 - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric - 6
EAN: 3389119405072
RM17TG20 - Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric
50,54 €
50,54 € incl. VAT
Text About:
Harmony control, phase sequence and loss, three-phase, 208-440VAC - Schneider Electric
50,54 €
SPECIFICATIONS
Main
product range Relais de contrôle Harmony
product specific application Pour alimentation triphasée
switching capacity in va 1250 VA
job category AC-12 se conformer à CEI 60947-5-1
AC-13 se conformer à CEI 60947-5-1
AC-14 se conformer à CEI 60947-5-1
AC-15 se conformer à CEI 60947-5-1
DC-12 se conformer à CEI 60947-5-1
DC-13 se conformer à CEI 60947-5-1
type of product or equipment Relais de contrôle 3 phases
rated output current 5 A
relay name RM17TG
[ui] rated insulation voltage 400 V se conformer à CEI 60664-1
parameters monitored by the relay Séquence de phases
Détection de défaillance de phase (coupure de 2 phases ou plus)
measuring range 208...440 V tension CA
voltage and type of control circuit 208...440 V
type of relay Relaisde contrôle
Complementary
contact description 2 "O/F"
response time <= 130 ms (en cas d'un défaut)
output contacts 2 "OF"
tightening torque 0,6…1 N.m se conformer à CEI 60947-1
case material Plastique auto-extinguible
minimum switching current 10 mA à 5 V CC
product weight 0,13 kg
marking CE
power consumed in va 0…22 VA à 400 V CA 50 Hz
connection mode Bornes à vis, 1 x 0,5 à 1 x 4 mm² (AWG 20 à AWG 11) rigide sans embout
Bornes à vis, 2 x 0,5 à 2 x 2,5 mm² (AWG 20 à AWG 14) rigide sans embout
Bornes à vis, 1 x 0,2 à 1 x 2,5 mm² (AWG 24 à AWG 12) souple avec embout
Bornes à vis, 2 x 0,2 à 2 x 1,5 mm² (AWG 24 à AWG 16) souple avec embout
safety reliability data B10d = 850000
MTTFd = 924,6 années
control circuit voltage range - 12 % + 10 % Un
mechanical endurance 30000000 cycle
width (w) 17,5 mm
control circuit frequency 50...60 Hz +/- 10 %
power frequency 50/60 Hz +/- 10 %
power-on delay 650 ms
supply voltage limits 183…484 V CA
delay Sans
Local signalling pourrelais allumé DEL (jaune)
measurement voltage limits 183…484 V CA
mounting bracket Rail DIN symétrique 35 mm se conformer à EN/CEI 60715
electrical stamina 10000 cycle
mounting position Toutes positions sans déclassement
voltage detection threshold < 100 V CA
voltage range of use 183...484 V
command speed <= 360 opérations/heure pleine charge
maximum cut-off voltage 250 V CA
250 V CC
Environment
degree of pollution 3 se conformer à CEI 60664-1
ip degree of protection IP20 se conformer à CEI 60529 (bornes)
IP30 se conformer à CEI 60529 (gaine)
product certificates GOST
C-Tick
UL
CSA
GL
electromagnetic compatibility Norme d'émission pour environnements industriels se conformer à EN/CEI 61000-6-4
Norme sur l'émission pour environnements résidentiel/commerciaux/industrie légèr se conformer à EN/CEI 61000-6-3
Immunité des environnements industriels se conformer à EN/CEI 61000-6-2
overvoltage category III se conformer à CEI 60664-1
standards EN/CEI 60255-1
relative humidity 95 % à 55 °C se conformer à CEI 60068-2-30
operating temperature -20…50 °C
storage room temperature -40…70 °C
mechanical shock resistance 15 gn pour 11 ms se conformer à CEI 60255-21-1
where of non-dissipative shock 4 kV
European regulation 73/23/CEE - directive basse tension
89/336/CEE - compatibilité électromagnétique
vibration resistance 0,35 mm (f= 5…57,6 Hz) se conformer à CEI 60068-2-6
1 gn (f= 57,6…150 Hz) se conformer à CEI 60255-21-1
dielectric test voltage 2 kV CA 50 Hz, 1 mn
insulation resistance > 500 MΩ à 500 V CC se conformer à CEI 60255-5
> 500 MΩ à 500 V CC se conformer à CEI 60664-1