Main
Measurement range
2...20 A current
Relay monitored parameters
Overcurrent detection
switching capacity in va
1250 VA
Relay type
Current control relay
relay name
RM17JC
[ui] rated insulation voltage
400 V conforming to IEC 60664-1
threshold setting
10...100 %
Complementary
maximum power consumption in va
3 VA
Product certifications
GL
C-Tick
GOST
UL
CSA
response time
< 200 ms (in the event of a fault)
output contacts
1 C/O
Product or component type
Current control relay
tightening torque
0.6…1 N.m conforming to IEC 60947-1
[us] rated supply voltage
24...240 V AC/DC 50/60 Hz +/- 10 %
Connections - terminals
Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
minimum switching current
10 mA at 5 V DC
marking
CE : 73/23/EEC
CE : EMC 89/336/EEC
Contacts material
Cadmium free
Delay at power up
0.5 s
hysteresis
15 % fixed of threshold setting
Contacts type and composition
1 C/O
input current
100000 mA permanent at 25 °C
300000 mA non repetitive < 3 s at 25 °C
maximum measuring cycle
30 ms measurement cycle as true rms value
width (w)
17.5 mm
control circuit frequency
40...70 Hz sinusoidal
supply voltage limits
20.4…264 V AC/DC
Local signalling
LED (green) for power ON
LED (yellow) for relay ON
Net weight
0.13 kg
measurement error
+/- 0.05 %/°C with temperature variation
< 1 % over the whole range with voltage variation
measurement accuracy
+/- 10 % of the full scale value
Operating position
Any position without derating
Immunity to microbreaks
10 ms
Mounting support
35 mm symmetrical DIN rail conforming to EN/IEC 60715
mechanical durability
30000000 cycles
electrical durability
100000 cycles
repeat accuracy
+/- 0.5 % for input and measurement circuit
Housing material
Self-extinguishing plastic
Pollution degree
3 conforming to IEC 60664-1
maximum power consumption in w
1 W
polarity
Yes DC
Maximum switching voltage
250 V AC/DC
Insulation
Between supply and measurement
Operating rate
<= 360 operations/hour full load
Shock resistance
15 gn for 11 ms conforming to IEC 60255-21-1
operating voltage tolerance
- 15 % + 10 % Un
Utilisation category
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
DC-14 conforming to IEC 60947-5-1
Nominal output current
5 A
Time delay
Without
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
Range of product
Harmony Control Relays
ambient air temperature for operation
-20…50 °C
electromagnetic compatibility
Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Non-dissipating shock wave
4 kV
overvoltage category
III conforming to IEC 60664-1
standards
EN/IEC 60255-6
relative humidity
95 % at 55 °C conforming to IEC 60068-2-30
vibration resistance
0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6
1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
dielectric test voltage
2 kV AC 50 Hz
insulation resistance
> 500 MOhm at 500 V DC conforming to IEC 60255-5
> 500 MOhm at 500 V DC conforming to IEC 60664-1