All categories
Compare Cart

RE22R2MXMU - Harmony, Modular timing relay, 8 A, 2 CO, 0.1 s?¦100 h, multifunction, 24 V DC / 24...240 V AC/DC - Schneider Electric

Expected in 2-4 weeks
RE22R2MXMU - Harmony, Modular timing relay, 8 A, 2 CO, 0.1 s?¦100 h, multifunction, 24 V DC / 24...240 V AC/DC - Schneider Electric - Harmony, Modular timing relay, 8 A, 2 CO, 0.1 s?¦100 h, multifunction, 24 V DC / 24...240 V AC/DC - Schneider Electric - 0
RE22R2MXMU - Harmony, Modular timing relay, 8 A, 2 CO, 0.1 s?¦100 h, multifunction, 24 V DC / 24...240 V AC/DC - Schneider Electric
77,05 € excl. VAT
94,00 € incl. VAT
Text About:
Harmony, Modular timing relay, 8 A, 2 CO, 0.1 s?¦100 h, multifunction, 24 V DC / 24...240 V AC/DC - Schneider Electric
94,00 €
SPECIFICATIONS
Main
Device short name RE22
Complementary
[ics] rated service breaking capacity 2000 VA
Control type Rotary knob front panel
maximum switching current 8 mA
Product certifications CSA
CCC
GL
cULus
EAC
CE
RCM
Product or component type Multifunction relay
tightening torque 0.6…1 N.m conforming to IEC 60947-1
[us] rated supply voltage 24...240 V AC
24 V DC
Connections - terminals Screw terminals, 2 x 1.5 mm² with cable end
Screw terminals, 2 x 2.5 mm² without cable end
minimum switching current 10 mA at 5 V
Contacts type and composition 1 C/O timed contact
1 C/O timed or instantaneous contact
safety reliability data B10d = 170000
MTTFd = 182.6 years
width (w) 22.5 mm
temperature drift +/- 0.05 %/°C
Net weight 0.09 kg
voltage drift +/- 0.2 %/V
Discrete output type Relay
Immunity to microbreaks 10 ms
Mounting support 35 mm DIN rail conforming to EN/IEC 60715
mechanical durability 10000000 cycles
electrical durability 100000 cycles for resistive load, 8 A at 250 V, AC
repeat accuracy +/- 0.5 % conforming to IEC 61812-1
control signal pulse width 30 ms
100 ms under load
Housing material Self-extinguishing
Power consumption in va 50 VA at 240 V AC
Power consumption in w 0.7 W at 24 V DC
Time delay range 0.1...1 s
1...10 h
1...10 s
6...60 min
10...100 h
6...60 s
1...10 min
mounting position Any position in relation to normal vertical mounting plane
Maximum switching voltage 250 V
dielectric strength 2.5 kV for 1 mA/1 minute at 50 Hz conforming to IEC 61812-1
recovery time 120 ms on de-energisation
rated impulse withstand voltage 5 kV for 1.2…50 µs conforming to IEC 60664-1
5 kV conforming to IEC 61812-1
Shock resistance 15 gn for 11 ms conforming to IEC 60068-2-27
Status led LED green (flashing) for timing in progress
LED green (steady) for power ON
LED yellow for relay energised
Supply frequency 50...60 Hz +/- 5 %
Power on delay 100 ms
Nominal output current 8 A
Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Time delay type Pulse delay
Safe-guard
Bistable
Interval
Voltage range 0.85...1.1 Us
Environment
Ambient air temp for storage/transportation -30…60 °C
Directives 2006/95/EC - low voltage directive
2004/108/EC - electromagnetic compatibility
ip degree of protection IP40 housing: conforming to IEC 60529
IP50 front face: conforming to IEC 60529
IP20 terminal block: conforming to IEC 60529
Range of product Harmony Timer Relays
ambient air temperature for operation -20…60 °C
electromagnetic compatibility Electrostatic discharge immunity test - test level: 6 kV level 3 (contact discharge) conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test - test level: 8 kV level 3 (air discharge) conforming to EN/IEC 61000-4-2
Fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC 61000-4-4
Fast transients immunity test - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4
Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6
Electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1 GHz) conforming to IEC 61000-4-3
Immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11
Immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11
standards IEC 61812-1
EN 61000-6-1
EN 61000-6-3
EN 61000-6-4
EN 61000-6-2
relative humidity 93 %, without condensation conforming to IEC 60068-2-30
vibration resistance 20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
insulation resistance 100 MOhm at 500 V DC conforming to IEC 60664-1