Complementary
																					
												Control type
												Rotary knob
Diagnostic button
											
                            
																					
												maximum switching current
												8 A
											
                            
																					
												Product certifications
												CSA
CCC
RCM
CE
GL
UL
EAC
											
                            
																					
												Product or component type
												Single function relay
											
                            
																					
												tightening torque
												0.6…1 N.m conforming to IEC 60947-1
											
                            
																					
												[us] rated supply voltage
												24...240 V AC/DC 50/60 Hz
											
                            
																					
												Connections - terminals
												Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
											
                            
																					
												minimum switching current
												10 mA at 5 V DC
											
                            
																					
												Contacts type and composition
												1 C/O timed or instantaneous contact, cadmium free
2 C/O timed contact, cadmium free
											
                            
																					
												safety reliability data
												MTTFd = 251.1 years
B10d = 230000
											
                            
																					
												width (w)
												22.5 mm
											
                            
																					
												Creepage distance
												4 kV/3 conforming to IEC 60664-1
											
                            
																					
												temperature drift
												+/- 0.05 %/°C
											
                            
																					
												Net weight
												0.105 kg
											
                            
																					
												voltage drift
												+/- 0.2 %/V
											
                            
																					
												Discrete output type
												Relay
											
                            
																					
												Immunity to microbreaks
												10 ms
											
                            
																					
												Mounting support
												35 mm DIN rail conforming to EN/IEC 60715
											
                            
																					
												mechanical durability
												10000000 cycles
											
                            
																					
												electrical durability
												100000 cycles, 8 A at 250 V, AC-1
100000 cycles, 2 A at 24 V, DC-1
											
                            
																					
												repeat accuracy
												+/- 0.5 % conforming to IEC 61812-1
											
                            
																					
												control signal pulse width
												100 ms with load in parallel
30 ms
											
                            
																					
												Housing material
												Self-extinguishing
											
                            
																					
												Pollution degree
												3 conforming to IEC 60664-1
											
                            
																					
												Power consumption in va
												3 VA at 240 V AC
											
                            
																					
												Power consumption in w
												1.5 W at 240 V DC
											
                            
																					
												Time delay range
												10...100 s
3...30 h
1...10 s
3...30 s
30...300 h
0.3...3 s
0.05...1 s
30...300 min
30...300 s
3...30 min
											
                            
																					
												mounting position
												Any position
											
                            
																					
												Maximum switching voltage
												250 V AC
											
                            
																					
												dielectric strength
												2.5 kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation conforming to IEC 61812-1
											
                            
																					
												recovery time
												120 ms on de-energisation
											
                            
																					
												rated impulse withstand voltage
												5 kV for 1.2…50 µs conforming to IEC 60664-1
											
                            
																					
												Shock resistance
												15 gn not operating for 11 ms conforming to IEC 60068-2-27
5 gn in operation for 11 ms conforming to IEC 60068-2-27
											
                            
																					
												Release input voltage
												<= 2.4 V
											
                            
																					
												Status led
												LED backlight green (steady) for dial pointer indication
LED yellow (steady) for output relay energised
LED yellow (fast flashing) for timing in progress and output relay de-energised
LED yellow (slow flashing) for timing in progress and output relay energised
											
                            
																					
												Supply frequency
												50...60 Hz +/- 5 %
											
                            
																					
												Power on delay
												100 ms
											
                            
																					
												Nominal output current
												8 A
											
                            
																					
												Setting accuracy of time delay
												+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
											
                            
																					
												Time delay type
												Off-delay
											
                            
																					
												Voltage range
												0.85...1.1 Us
											
                            
																			 
																	
										Environment
																					
												Ambient air temp for storage/transportation
												-40…70 °C
											
                            
																					
												Directives
												2006/95/EC - low voltage directive
2004/108/EC - electromagnetic compatibility
											
                            
																					
												ip degree of protection
												IP40 housing: conforming to IEC 60529
IP20 terminals: conforming to IEC 60529
IP50 front panel: conforming to IEC 60529
											
                            
																					
												Range of product
												Harmony Timer Relays
											
                            
																					
												ambient air temperature for operation
												-20…60 °C
											
                            
																					
												electromagnetic compatibility
												Fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC 61000-4-4
Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1 GHz) conforming to IEC 61000-4-3
Conducted RF disturbances - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6
Fast transient bursts - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4
Immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11
Immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11
											
                            
																					
												overvoltage category
												III conforming to IEC 60664-1
											
                            
																					
												standards
												UL 508
IEC 61812-1
											
                            
																					
												relative humidity
												95 % at 25…55 °C
											
                            
																					
												vibration resistance
												20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
											
                            
																					
												insulation resistance
												100 MOhm at 500 V DC conforming to IEC 60664-1