Complementary
																					
												[ics] rated service breaking capacity
												2000 VA
											
                            
																					
												Control type
												Rotary knob front panel
											
                            
																					
												maximum switching current
												8 mA
											
                            
																					
												Product certifications
												cULus
RCM
CSA
EAC
GL
CCC
CE
											
                            
																					
												Product or component type
												Single function relay
											
                            
																					
												tightening torque
												0.6…1 N.m conforming to IEC 60947-1
											
                            
																					
												[us] rated supply voltage
												380...440 V AC
230...240 V AC
											
                            
																					
												Connections - terminals
												Screw terminals, 2 x 1.5 mm² with cable end
Screw terminals, 2 x 2.5 mm² without cable end
											
                            
																					
												minimum switching current
												10 mA at 5 V
											
                            
																					
												Contacts type and composition
												1 C/O timed contact
											
                            
																					
												safety reliability data
												B10d = 260000
MTTFd = 273.9 years
											
                            
																					
												width (w)
												22.5 mm
											
                            
																					
												temperature drift
												+/- 0.05 %/°C
											
                            
																					
												Net weight
												0.093 kg
											
                            
																					
												voltage drift
												+/- 0.2 %/V
											
                            
																					
												Discrete output type
												Relay
											
                            
																					
												Immunity to microbreaks
												10 ms
											
                            
																					
												Mounting support
												35 mm DIN rail conforming to EN/IEC 60715
											
                            
																					
												mechanical durability
												10000000 cycles
											
                            
																					
												electrical durability
												100000 cycles for resistive load, 8 A at 250 V, AC
											
                            
																					
												repeat accuracy
												+/- 0.5 % conforming to IEC 61812-1
											
                            
																					
												control signal pulse width
												30 ms
100 ms under load
											
                            
																					
												Housing material
												Self-extinguishing
											
                            
																					
												Power consumption in va
												8 VA at 230...240 V
17 VA at 380...440 V
											
                            
																					
												Time delay range
												1...10 h
10...100 h
6...60 s
1...10 min
0.1...1 s
1...10 s
6...60 min
											
                            
																					
												mounting position
												Any position in relation to normal vertical mounting plane
											
                            
																					
												Maximum switching voltage
												250 V
											
                            
																					
												dielectric strength
												2.5 kV for 1 mA/1 minute at 50 Hz conforming to IEC 61812-1
											
                            
																					
												recovery time
												120 ms on de-energisation
											
                            
																					
												rated impulse withstand voltage
												5 kV for 1.2…50 µs conforming to IEC 60664-1
5 kV conforming to IEC 61812-1
											
                            
																					
												Shock resistance
												15 gn for 11 ms conforming to IEC 60068-2-27
											
                            
																					
												Status led
												LED green (flashing) for timing in progress
LED green (steady) for power ON
LED yellow for relay energised
											
                            
																					
												Supply frequency
												50...60 Hz +/- 5 %
											
                            
																					
												Power on delay
												100 ms
											
                            
																					
												Nominal output current
												8 A
											
                            
																					
												Setting accuracy of time delay
												+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
											
                            
																					
												Time delay type
												Star-delta
											
                            
																					
												Voltage range
												0.85...1.1 Us
											
                            
																			 
																	
										Environment
																					
												Ambient air temp for storage/transportation
												-30…60 °C
											
                            
																					
												Directives
												2004/108/EC - electromagnetic compatibility
2006/95/EC - low voltage directive
											
                            
																					
												ip degree of protection
												IP40 housing: conforming to IEC 60529
IP20 terminal block: conforming to IEC 60529
IP40 front face: conforming to IEC 60529
											
                            
																					
												Range of product
												Harmony Timer Relays
											
                            
																					
												ambient air temperature for operation
												-20…60 °C
											
                            
																					
												electromagnetic compatibility
												Electrostatic discharge immunity test - test level: 6 kV level 3 (contact discharge) conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test - test level: 8 kV level 3 (air discharge) conforming to EN/IEC 61000-4-2
Fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC 61000-4-4
Fast transients immunity test - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4
Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6
Electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1 GHz) conforming to IEC 61000-4-3
Immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11
Immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11
Conducted and radiated emissions class B conforming to EN 55022
											
                            
																					
												standards
												EN 61000-6-4
IEC 61812-1
EN 61000-6-1
EN 61000-6-3
EN 61000-6-2
											
                            
																					
												relative humidity
												93 %, without condensation conforming to IEC 60068-2-30
											
                            
																					
												vibration resistance
												20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
											
                            
																					
												insulation resistance
												100 MOhm at 500 V DC conforming to IEC 60664-1