Complementary
compatibility code
RE17
[ics] rated service breaking capacity
2000 VA
Control type
Selector switch front panel
maximum switching current
8 A AC/DC
Product certifications
CSA
GL
cULus
Handle front plate colour
90 mm
Product or component type
Multifunction relay
tightening torque
0.6…1 N.m conforming to IEC 60947-1
[uimp] rated impulse withstand voltage
5 kV during 1.2/50 µs
[us] rated supply voltage
12 V AC/DC 50/60 Hz
Connections - terminals
Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
minimum switching current
10 mA at 5 V DC
marking
CE
reset time
120 ms on de-energisation typical
Contacts material
Cadmium free
Contacts type and composition
1 C/O
safety reliability data
MTTFd = 296.8 years
B10d = 270000
width (w)
17.5 mm
On-load factor
100 %
Creepage distance
4 kV/3 conforming to IEC 60664-1
Local signalling
LED indicator for on steady: relay energised, no timing in progress
LED indicator for flashing: timing in progress 80 % ON and 20 % OFF
LED indicator for pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) 5 % ON and 95 % OFF
temperature drift
+/- 0.05 %/°C
Net weight
0.07 kg
voltage drift
+/- 0.2 %/V
Discrete output type
Relay
functionality
Multifunction
Immunity to microbreaks
20 ms
Mounting support
35 mm DIN rail conforming to EN/IEC 60715
depth
72 mm
mechanical durability
10000000 cycles
electrical durability
100000 cycles (8 A at 250 V AC maximum) for resistive load
operating frequency
10 Hz
repeat accuracy
+/- 0.5 % conforming to IEC 61812-1
control signal pulse width
100 ms with load in parallel typical
30 ms typical
Housing material
Self-extinguishing
Power consumption in va
0…0.7 VA at 12 V AC
Time delay range
1...10 s
6...60 s
10...100 h
1...10 min
1...10 h
0.1...1 s
6...60 min
mounting position
Any position in relation to normal vertical mounting plane
maximum power consumption in w
0.5 W at 12 V DC
Maximum switching voltage
250 V AC
dielectric strength
2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Supply frequency
50...60 Hz +/- 5 %
Power on delay
100 ms
Release of input voltage
5 V
Nominal output current
8 A
Setting accuracy of time delay
+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Time delay type
A, Ac, At, B, Bw, C, D, Di, H, Ht
Voltage range
0.9...1.2 Us
Environment
Ambient air temp for storage/transportation
-30…60 °C
ip degree of protection
IP20 (terminal block) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529
Range of product
Harmony Timer Relays
ambient air temperature for operation
-20…60 °C
electromagnetic compatibility
Electrostatic discharge immunity test: (in contact), level 3, 6 kV, conforming to IEC 61000-4-2
Electrostatic discharge immunity test: (in air), level 3, 8 kV, conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields: (80 MHz to 1 GHz), level 3, 10 V/m, conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test: (capacitive connecting clip), level 3, 1 kV, conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test: (direct), level 3, 2 kV, conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test: (differential mode), level 3, 1 kV, conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test: (common mode), level 3, 2 kV, conforming to IEC 61000-4-5
Conducted RF disturbances: (0.15...80 MHz), level 3, 10 V, conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test: (1 cycle), 0 %, conforming to IEC 61000-4-11
Voltage dips and interruptions immunity test: (25/30 cycles), 70 %, conforming to IEC 61000-4-11
Conducted and radiated emissions: , class B, conforming to EN 55022
standards
2006/95/EC
2004/108/EC
EN 61000-6-4
EN 61000-6-1
EN 61000-6-3
IEC 61812-1
EN 61000-6-2
relative humidity
93 % without condensation conforming to IEC 60068-2-30
vibration resistance
20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
insulation resistance
100 MOhm at 500 V DC conforming to IEC 60664-1